E50H2, E50H5 Installation Guide
BACnet Programming Information (cont.)
By default, the Record_Count property of the Trend_Log objects is initialized to Zero.
Reading Data:
Access logged data with corresponding timestamps via the Log_Buffer property of the Trend_Log object using the BACnet ReadRange service. The E50H5 supports both the
"by Position" and "by Sequence Number" modes of the ReadRange service, but not the "by Time" mode.
Trend_Log Objects
Trend_Log Properties
R/W
Used
Object_Name
R
Description
R
Log_Enable
W
Start_Time
W
Stop_Time
W
Log_Device_Object_
W
Property
Log_Interval
W
Stop_When_Full
W
Buffer_Size
R
Log_Buffer
R
Record_Count
W
Total_Record_Count
R
Event_State
R
ZL0071-0F
Page 27 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Units
Trend_Log_<n>
Trend_Log <n>
Binary
Date/Time
Date/Time
BACnetDeviceObjectProptertyReference
0.01 seconds
Binary
5760
List of BACnetLongRecord
Unsigned 32-bit integer
Unsigned 32-bit integer
Binary
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Additional information
Where n is 1-3 (there are three instances of Trend_Log objects available)
Where n is 1-3 (there are three instances of Trend_Log objects available)
Set this to TRUE to enable logging or FALSE to disable logging. The default is TRUE.
The value is set to FALSE internally if logging stops for other reasons (i.e. buffer is full).
Sets the Date/Time when data logging will Start (if Log_enable is TRUE). Set to a Date/Time earlier
than the Local_Date/Local_Time properites of the Device object and Set Log_Enable TRUE to start
logging immediately.
Sets the Date/Time when data Logging will STOP (if still running).
Stop_Time will be ignored if "wildcard" values are used in any of the fields.
Set (point) this to the Present_Value of any of objects AI1 through AI49
to establish which parameter to log. Default values are:
TL1 = Real Energy Consumption (Array of AI1 Present_Value)
TL2 = Reactive Energy Consumption (Array of AI27 Present_Value)
TL3 = Total Real Power Present Demand (Array of AI34 Present_Value)
Logging period in hundredths of a second.
Default is 90000 (15 minute intervals); minimum value is 1000 (10 seconds). This property can also
be set to Zero, which changes all three Trend_Logs and the Demand calculation to a manual mode
(sometimes referred to as "Sync to Comms"). In manual mode, the demand interval is updated and
another record is logged upon a manual command, which is issued by writing the value 21211 to the
Present_Value of object AV1.
Set this to TRUE to stop logging when the buffer is full (single-shot mode) or FALSE to continue when
full (wrap & overwtrite oldest data entries).
Length of Log Data buffer (# of records).
Contains the data values logged, with timestamps
This is an integer count of how many records logged since the Trend_Log objects were last reset.
Writing a Zero to this property resets the logs of all three objects. This value defaults to Zero, but, by
default, logging starts automatically at 15 minute intervals.
This is an integer count of how many records logged since the Trend_Log objects were created (the
factory state of the meter). This count is unaffected by resetting the Record Count or by power
failures.