Veris Industries E50H Series Installation Manual page 23

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

E50H2, E50H5 Installation Guide
BACnet Programming Information (cont.)
Analog_Input Objects
Use the Present_Value property of the Analog_Input objects for all read-only numeric variables in the meter other than those used specifically for device configuration (in the
Device Object) or data logging (in the Trend_Log objects). Only the E50H5 supports the data logging capability.
These objects support the Description and Reliability object properties and all required Analog_Input object properties. None of them are writable. The values that are not
instantaneous (i.e., Accumulated Energy, Max Demand, Pulse Input Counts) are non-volatile. They are not updated while control power is inactive, but their past values are
retained when power is restored. The Present_Value of the accumulated data objects (AI1, AI26-AI27 and AI42-AI44) use floating-point data types (all AI objects use floating
point data points). The resolution of the accumulated values decreases as the value grows larger over time and more of the significant digits precede the decimal point. If the
size of the value limits the resolution unacceptably, read and store the current value offline and reset the accumulators to restore finer resolution.
For complete assurance, check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value. If the line voltage or input frequency of the system
being monitored falls out of the supported range, the corresponding alert bits (BI1-BI7) are set and the reliability property of any values that cannot be accurately measured
under those conditions returns Unreliable_Other.
#
Object_Name
Description
AI1
Energy
Real Energy
Consumption
AI2
kW_Total
Total Real Power
AI3
kVAR_Total
Total Reactive Power
AI4
kVA_Total
Total Apparent Power R
AI5
PF_Total
Total Power Factor
AI6
Volts_LL_Avg
Voltage L-L Average
AI7
Volts_LN_Avg
Voltage L-N Average
AI8
Current_Avg
Current Average
AI9
kW_A
Real Power Phase A
AI10
kW_B
Real Power Phase B
AI11
kW_C
Real Power Phase C
AI12
PF_A
Power Factor Phase A R
AI13
PF_B
Power Factor Phase B R
AI14
PF_C
Power Factor Phase C
AI15
Volts_AB
Votlage Phase A-B
AI16
Volts_BC
Voltage Phase B-C
AI17
Volts_AC
Voltage Phase A-C
AI18
Volts_AN
Voltage Phase A-N
AI19
Volts_BN
Voltage Phase B-N
AI20
Volts_CN
Voltage Phase C-N
AI21
Current_A
Current Phase A
AI22
Current_B
Current Phase B
AI23
Current_C
Current Phase C
AI24
Reserved_AI24
Reserved
AI25
Frequency
Frequency
ZL0071-0F
Page 23 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
R/W
NV
Units
R
NV
kWh
0 - 3.4+E38
R
kW
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
kVA
0 - Max_Power (AI45)
R
Power
0.00 - 1.00
Factor
R
Volts
R
Volts
R
Amps
R
kW
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
Power
0.00 - 1.00
Factor
Power
0.00 - 1.00
Factor
R
Power
0.00 - 1.00
Factor
R
Volts
R
Volts
R
Volts
R
Volts
R
Volts
R
Volts
R
Amps
R
Amps
R
Amps
R
n/a
R
Hz
45.0-65.0
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
1.00 for 100%
1.00 for 100%
1.00 for 100%
1.00 for 100%
Returns QNAN or any value
Returns QNAN if frequency is out of range (or no voltage
input present on Phase A)
Additional information