Veris Industries E50H Series Installation Manual page 2

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

E50H2, E50H5 Installation Guide
Specifications
(cont.)
ZL0071-0F
Page 2 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
DC*
Ride Through Time
Pulse
Minimum Pulse Width
Alarm Contacts (E50H2 only)
RS-485 Port
Weight
IP Degree of Protection
(IEC 60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Rail
Operating Temperature Range
Storage Temperature Range
Humidity Range
Altitude of Operation
Mounting Location
US and Canada
Dielectric Withstand
Conducted and Radiated Emissions
Conducted and Radiated Immunity
US and Canada (cULus)
Europe (CE)
* External DC current limiting is required, see fuse recommendations.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
CONTROL POWER
AC
5 VA max.; 90 V min.
UL Maximum: 600 V
(347 V
); CE Maximum: 300 V
L-L
L-N
3 W max.; UL and CE: 125 to 300VDC
100 msec at 120 Vac
INPUT
Solid-state or mechanical contacts (current less than 1 mA);
E50H2: 1 pulse input; E50H5: 2 pulse inputs
20 msec
OUTPUT
N.C., static output; (30 Vac/dc, 100 mA max. @ 25 °C, derate 0.56 mA per °C
above 25 °C)
2-wire, 9600 to 115.2 kbaud, BACnet MS/TP
MECHANICAL CHARACTERISTICS
0.62 lb (0.28 kg)
IP40 front display; IP20 meter
Back-lit blue LCD
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
24 to 14 AWG (0.2 to 2.1 mm
)
2
T35 (35 mm) DIN rail per EN 50022
OPERATING CONDITIONS
-30 to 70 °C (-22 to 158 °F)
-40 to 85 °C (-40 to 185 °F)
<95% RH non-condensing
3000 m
Not suitable for wet locations. For indoor use only.
COMPLIANCE INFORMATION
CAT III, Pollution Degree 2;
for distribution systems up to 347 V
CE
CAT III, Pollution Degree 2;
for distribution systems up to 300 V
Per UL 508, IEC/EN 61010-1
FCC part 15 Class B, EN 55011/EN 61000 Class B (residential and light
industrial)
EN 61000 Class A (heavy industrial)
UL 508 (open type device)/CSA 22.2 No. 14-05
IEC/EN 61010-1
L-N
/600 Vac
L-N
L-L
L-N
TM
0818

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50h2E50h5

Table of Contents