Bacnet Pics - Veris Industries E31E84 Installation Manual

Branch circuit power meter with ethernet communication
Table of Contents

Advertisement

E31E Series Installation Guide

BACnet PICS

Z206855-0D
Page 26 of 35
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
BACnet PICS (Protocol Implementation Conformance Statement)
Vendor Name: Veris Industries
BACnet Vendor ID 133
Product Name: E31E Series Branch Circuit Monitor
Product Model Number: <Model Number>
Product Description: Branch Circuit Monitor
BACnet Protocol Version: Version 1 Revision 12
BACnet Standardized Device Profile (Annex L) - [Note: E31E incorporates a gateway device]
• BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
• K.1.2 BIBB - Data Sharing - ReadProperty-B (DS-RP-B)
• K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
• K.1.8 BIBB - Data Sharing - WriteProperty-B (DS-WP-B)
• K.1.10 BIBB - Data Sharing - WritePropertyMultiple-B (DS-WPM-B)
• K.1.12 BIBB - Data Sharing - COV-B (DS-COV-B)
• K.2.2 BIBB - Alarm and Event-Notification Internal-B (AE-N-I-B)
• K.2.5 BIBB - Alarm and Event-ACK-B (AE-ACK-B)
• K.2.11 BIBB - Alarm and Event-Information-B (AE-INFO-B)
• K.5.2 BIBB - Device Management - Dynamic Device Binding-B (DM-DDB-B)
• K.5.4 BIBB - Device Management - Dynamic Object Binding-B (DM-DOB-B)
• K.5.6 BIBB - Device Management - DeviceCommunicationControl-B (DM-DCC-B)
• K.5.12 BIBB - Device Management - TimeSyncronization-B (DM-TS-B)
• K.5.22 BIBB - Device Management - List Manipulation-B (DM-LM-B)
• K.5.20 BIBB - Device Management - Restart-B (DM-R-B)
Standard Object Types Supported
• Device Object
• Analog Input
• Analog Output
• Analog Value
Unsupported Properties and Restrictions
• Does not support BACnet CreateObject
• Does not support BACnet DeleteObject
• Does not support any proprietary properties
• No proprietary properties exist
• No range restrictions exist
• Max_Master is writable
Data Link Layer Options:
• BACnet IP, (Annex J)
• MS/TP master (Clause 9), baud rate up to 76.8 kbps
Networking Options:
• BACnet/IP Broadcast Management Device (BBMD)
• Registrations by Foreign Devices
Character Sets Supported:
• ISO 10646 (UTF-8) / ANSI X3.4
©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
TM
0420

Advertisement

Table of Contents
loading

This manual is also suitable for:

E31e seriesE31e42E31e004E31e002

Table of Contents