BACnet PICS (Protocol Implementation Conformance Statement)
Vendor Name: Veris Industries
BACnet Vendor ID 133
Product Name: E30E Series Branch Circuit Monitor
Product Model Number: <Model Number>
Product Description: Branch Circuit Monitor
BACnet Protocol Version: Version 1 Revision 12
BACnet Standardized Device Profile (Annex L) – [Note: E30E incorporates a gateway device]
• BACnet Application Specific Controller (B‐ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
• K.1.2 BIBB ‐ Data Sharing ‐ ReadProperty‐B (DS‐RP‐B)
• K.1.4 BIBB ‐ Data Sharing ‐ ReadPropertyMultiple‐B (DS‐RPM‐B)
• K.1.8 BIBB ‐ Data Sharing ‐ WriteProperty‐B (DS‐WP‐B)
• K.1.10 BIBB ‐ Data Sharing ‐ WritePropertyMultiple‐B (DS‐WPM‐B)
• K.1.12 BIBB ‐ Data Sharing ‐ COV‐B (DS‐COV‐B)
• K.2.2 BIBB ‐ Alarm and Event‐Notification Internal‐B (AE‐N‐I‐B)
• K.2.5 BIBB ‐ Alarm and Event‐ACK‐B (AE‐ACK‐B)
• K.2.11 BIBB ‐ Alarm and Event‐Information‐B (AE‐INFO‐B)
• K.5.2 BIBB ‐ Device Management ‐ Dynamic Device Binding‐B (DM‐DDB‐B)
• K.5.4 BIBB ‐ Device Management ‐ Dynamic Object Binding‐B (DM‐DOB‐B)
• K.5.6 BIBB ‐ Device Management ‐ DeviceCommunicationControl‐B (DM‐DCC‐B)
• K.5.12 BIBB ‐ Device Management ‐ TimeSyncronization‐B (DM‐TS‐B)
• K.5.22 BIBB ‐ Device Management – List Manipulation‐B (DM‐LM‐B)
Standard Object Types Supported
• Device Object
• Analog Input
• Analog Output
• Analog Value
Unsupported Properties and Restrictions
• Does not support BACnet CreateObject
• Does not support BACnet DeleteObject
• Does not support any proprietary properties
• No proprietary properties exist
• No range restrictions exist
• Max_Master is writable
Data Link Layer Options:
• BACnet IP, (Annex J)
• MS/TP master (Clause 9), baud rate up to 76.8 kbps
Networking Options:
• BACnet/IP Broadcast Management Device (BBMD)
• Registrations by Foreign Devices
Character Sets Supported:
• ISO 10646 (UTF-8) / ANSI X3.4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.calcert.com
15
10
20
5
25
0
30
sales@calcert.com
TM
04142

Advertisement

Table of Contents
loading

Table of Contents