Example 3. Read The Vf-Mb1/S15/As3 Parameter - Toshiba TOSVERT VF-MB1 Function Manual

Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

9.3. Example 3. Read the VF-MB1/S15/AS3 parameter

When access to VF-MB1/S15/AS3 parameter, set "1000" to the PNU.
9.3.1.
Write Request data table (Read
Header DU0
Header DU1
Header DU2
Header DU3
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Address (Byte 1)
Parameter Address (Byte 2)
Parameter Address (Byte 3)
Parameter Address (Byte 4)
Parameter Address (Byte 5)
Parameter Address (Byte 6)
* Refer to Appendix.
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-MB1/S15/AS3 parameter.
9.3.2.
Read Response data table (positive)
Header DU0
Header DU1
Header DU2
Header DU3
Request Header (Byte 1)
Request Header (Byte 2)
Request Header (Byte 3)
Request Header (Byte 4)
Parameter Value (Byte 1)
Parameter Value (Byte 2)
Parameter Value (Byte 3)
Parameter Value (Byte 4)
* Refer to Appendix.
** Value 0x31EC is "12780" in decimal. This means "127.80 (%)".
fd04
Field
Function number
Slot number (0)
Index (47)
Length
Request Reference
Request ID (0x01: Request) *
Axis
Number of Parameters
Attribute
Number of Elements
Parameter number, High byte **
Parameter number, Low byte **
VF-MB1/S15/AS3 Parameter number, High
byte
VF-MB1/S15/AS3 Parameter number, Low
byte
Field
Function number
Slot number (0)
Index (47)
Length
Request Reference (mirrored)
Response ID *
Axis (mirrored)
Number of Parameters
Format *
Number of Values
Values, High byte
Values, High byte
(Input voltage))
Description
Description
- 42 -
E6581738④
Value
0x5F
0x00
0x2F
0x0A
0x01
0x01
0x01
0x01
0x10
0x01
0x03
0xE8
0xFD
0x04
Value
0x5E
0x00
0x2F
0x08
0x01
0x01
0x01
0x01
0x42
0x01
0x31 **
0xEC **