Toshiba TOSVERT VF-MB1 Function Manual page 35

Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

Coast stop (ST =
11
OFF)
12
Emergency stop
13
Standby ST=ON
14
Standby
HAND/AUTO
15
(LOC/REM)
fd00 (Output frequency (real time))
7.5.11.
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- fd22 (Feedback value of PID (real time)).............................. Unit: 0.01Hz
- fd16 (Estimated speed (real time)) ....................................... Unit: 0.01Hz
- fd29 (Input power (real time)) ............................................... Unit: 0.01kW
- fd30 (Output power (real time)) ............................................ Unit: 0.01kW
fd03 (Output current (real time))
7.5.12.
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal
number) is read out.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
- fd05 (Output voltage (real time)) ............................................. Unit: 0.01% (V)
- fd04 (Voltage at DC bus (real time)) ....................................... Unit: 0.01% (V)
- fd18 (Torque) .......................................................................... Unit: 0.01% (Nm)*
* When the motor information connected to the drive set to the parameter (f405 - f415), torque
monitor value "100%" is same as the rated torque of a motor in general.
fe35, fe36, fe37 (Monitoring of the analog input)
7.5.13.
VF-MB1/S15
VIA input value: "Communication Number fe35"
VIB input value: "Communication Number fe36"
VIC input value: "Communication Number fe37"
These monitors can also be used as A/D converters irrespective of the inverter's control.
ST=ON
ST=OFF
No emergency
Emergency stop
stop status
status
Start-up process Standby
Start-up process Standby
AUTO
HAND
(LOC)
(REM)
- 33 -
E6581738④
-
-
Standby: Initialization completed,
not failure stop status, not alarm
stop status (moff], , [coff],
[coff], [lstp]), ST =ON and
RUN=ON
Standby: Initialization completed, not
failure stop status and not alarm stop
status ([MOFF], [coff], [coff],
[lstp])
Enabled with [f750]="2"
HAND: Panel operation is enabled
AUTO: Operation method selected
[cmod] and [fmod] are enabled.
Enabled with [f732]="0"
LOC: Panel operation is enabled
REM: Operation method selected
[cmod] and [fmod] are enabled.