5. VF-MB1/S15/AS3 Communication parameters

In a network, VF-MB1/S15/AS3 (PDP003Z) serves as a PROFIBUS slave device.
PDP003Z configuration is set by the following parameters.
Parameter
Function
c150
PDP003Z
Station address
c151
PDP003Z
Baud rate Monitor
c152
PDP003Z
Profile Monitor
c154
JOG1 Frequency
(STW.8)
c155
JOG2 Frequency
(STW.9)
c156
Tmax
(ZSW.8)
c157
Tolerance
(ZSW.8)
c100
Communication error
detection delay time
c101
Drive operation at the
communications
loss action
(Network wire breaks)
c102
Preset speed
operation selection
c103 **
Communication
time-out condition
selection
f899
Network option
reset setting
fd67
PDP003Z version
*
Do not set at VF-MB1 V1.00.
**
It is necessary to enable "Watchdog" function with the configurator.
***
When the parameters are changed or to reset
After reset, the parameter changes become effective.
Set 1
f899
to
fmod
****
When
or
(STW Bit 13) or
Reference
Please note that drive keeps driving when the communication is lost if
the parameter
Caution
2 to 126
The station address "126" cannot exchange data.
0: 12 Mbit/s
1: 6 Mbit/s
2: 3 Mbit/s
3: 1.5 Mbit/s
4: 500 kbit/s
5: 187.5 kbit/s
6: 93.75 kbit/s
7: 19.2 kbit/s
8: 9.6 kbit/s
9: 45.45 kbit/s (Only for the VF-AS3)
0:Telegram 1 (PROFIdrive)
1:Telegram 100 (Vender Spec. 1)
2:Telegram 101 (Vender Spec. 2)
3:Telegram 102 (Vender Spec. 3)
0.0 to 20.0Hz
0.0 to 20.0Hz
0.1 to 60.0s
0.1 to 99.0%
0.0 to 100.0 sec
0: Stop and Communication release *
cmod
(follows
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation frequency set
c102
with
0: None
1 to 15: Preset speed (
0: Disconnection detection
1: When communication mode enable (Both
fmod
are set CANopen or COM option)
2: 1+Driving operation
0: None
1: Resetting the PDP003Z and the drive
PDP003Z firmware version
(ex. 0x1101 means "V1.01")
by the PROFIBUS communication might not be able to be set.
is set to "Communication option", VF-MB1/S15/AS3 drives without
cmod
(STW Bit 12) at PROFIdrive.
Net Control
c101
(Drive operation at the communications loss action).
Adjustment range
fmod
and
setting)
)
sr1
sr7
-
,
err8
, the power must be cycled (or set
- 11 -
E6581738④
f287
f295
-
)
cmod
and
f899
to 1).
1
(None) is set to
Default
setting
126
-
-
5.0Hz
5.0Hz
10.0s
50.0%
0.0
4
0
1
0
-
Net