6.6. Access to VF-MB1/S15/AS3 parameter

When access to VF-MB1/S15/AS3 parameter, set "1" to the PNU. The communication
number of the drive parameter is set to the sub-index IND.
Refer to the drive instruction manual about the communication number and unit.
* This procedure changes the value of VF-MB1/S15/AS3 EEPROM.
When you use this method for parameter writing, the value is written to the EEPROM.
6.6.1.
Examples of reading or changing VF-MB1/S15/AS3 parameter
6.6.1.1. Example 1. Reading the basic parameter (
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0003 (
PKE
0
Requirement
PKW
PKE
60
Response (Value: 0x0001 = Operation panel))
40
6.6.1.2. Example 2. Reading the extended parameter (
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 1
IND = 0x0219 (
PKE
0
Requirement
PKW
PKE
60
Response (Value: 0x1770 (= 6000 -> 60.00Hz *))
40
* "0x1770" as reading value of "VIC(VF-MB1,VF-S15) / II(VF-AS3) input point 2 frequency"
is 0x1770 = 6000 (decimal number)
Since the unit of "VIC(VF-MB1,VF-S15) / II(VF-AS3) input point 2 frequency" is 0.01Hz,
set the following value. 6000×0.01 = 60.00Hz
cmod
communication number)
1
1
0
0
6
IND
01
00
03
01
00
03
frequency))
f219
communication number)
1
1
0
0
6
IND
01
02
19
01
02
19
Notes
cmod
(command mode selection))
0
0
0
0
0
PWE
00
00
00
00
00
00
f219
(VIC(MB1,S15) / II(AS3) input point 2
0
0
0
0
0
PWE
00
00
00
00
00
17
- 22 -
E6581738④
0
0
0
0
0
0
PZD
・・・
・・・
00
・・・
・・・
01
0
0
0
0
0
0
PZD
・・・
・・・
00
・・・
・・・
70
0
1
1
0
1
1