Setting And Checking Of Run Timer And Stop Timer Function - SMC Networks HRSH090 Series Operation Manual

Thermo chiller
Hide thumbs Also See for HRSH090 Series:
Table of Contents

Advertisement

HRX-OM-R026
Chapter 5
Display and setting of various functions
5.7.2

Setting and checking of Run timer and stop timer function

Display
Item
Run timer
Stop timer
1.
Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for key-lock [
digital display.
PV
SV
Run timer Setting and checking
2.
Press the [SEL] key once.
The set screen of run timer is displayed on the digital display.
PV
SV
3.
Set the run timer as the table below with [▲] key or [▼] key, and confirm by pressing
"SEL".
Set value
to
E.g. Set at 5:30pm the previous day. Operation starts 14 hours later (7:30am the next
day).
PV
SV
5.7 Run timer, stop timer function
5-18
The table below explains the setting items of the run/stop timer and the initial
values.
Table 5.7-1 List of set run timer and stop timer
Sets run timer.
Sets stop timer.
This part explains the setting and checking items of both the run and stop
timers. Please refer to the applicable items for the timer you wish to use.
[MENU]
Press and
hold
PV
SV
Table 5.7-2 List of set value
Explanation
Timer OFF
Operation starts after set time.
Setting unit is 0.5 hour
Contents
[MENU]
Press and
hold
Initial value
(Default setting)
0.0H
0.0H
] appears on the
PV
SV
Initial value
(Default setting)
HRSH Series