Summary of Contents for SMC Networks HRSH090 Series
Page 1
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Series Inverter Type Power consumption reduced by (Only 400 VAC type) (UL Standard) the triple inverter! Outstanding energy saving due to RoHS Non-inverter chiller compressor compressor DC inverter DC inverter Compressor Compressor DC inverter DC inverter Pump Compressor + Fan + Others...
Page 2
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Triple inverter DC inverter compressor The inverter respectively controls the number of motor rotations of the compres- sor, fan and pump depending on the load from the user’s equipment. reduced by DC inverter Inverter Power...
Page 3
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Variations Cooling Cooling Optional International 149 to 152 Model Power supply Option Pages Page method capacity accessories standards · Piping conversion · With earth fitting leakage breaker Air-cooled · Bypass piping set 9.5 kW (For 400 V type as refrigeration...
Page 4
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Simple operation Compact and lightweight Reduced-height double condenser structure Step Press the key. Step Adjust the temperature setting with keys. Current Achieved a maximum Step Press the key to stop. reduction in the height Multiple air-cooled of the product while Easy operation by these steps...
Page 5
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Globally compatible power supplies Shaped for easy supply of circulating fluid (400 V type only) Filter for circulating fluid fill port (Optional accessory on page 151) (Europe, Asia, Oceania, Central and South America) ∗...
Page 6
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Convenient functions (Refer to the Operation Manual for details.) Timer operation function Unit conversion function Power failure auto-restart function Automatic restart from stoppage due to pow- Timer for ON and OFF can be set in Temperature and pressure units can be er failure, etc.
Page 7
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Communication function The serial communication (RS232C/RS485) and contact I/Os (2 inputs and 3 outputs) are equipped as standard. Communication with the user’s equipment and system construction are possible, depending on the application. A 24 VDC output can be also provided, and is available for a flow switch (SMC’s PF2W, etc.).
Page 8
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Global Supply Network SMC has a comprehensive network in the global market. We now have a presence of more than 500 branch offices and distributors in 83 countries world wide such as Asia, Oceania, North/Central/South America, and Europe.
Page 9
Circulating Fluid Temperature Controller Thermo-chiller HRSH090 Inverter Type Series Circulating Fluid/Facility Water Line Equipment Circulating Fluid Line Power supply (24 VDC) available Terminal block Particle Filter Circulating fluid return port Y-strainer Bypass valve User’s Pressure Switch Flow Switch equipment Valve Fittings and Tubing Circulating fluid outlet...
C O N T E N T S HRSH090 Series Inverter Type HRSH090 Thermo-chiller Series Optional Accessories How to Order/Specifications ......Page 141 q Piping Conversion Fitting ......Page 149 Air-cooled 200 V/400 V ......Page 142 w Bypass Piping Set ........Page 149 Water-cooled 200 V/400 V Cooling Capacity ..........
Thermo-chiller Inverter Type (400 V type only) (UL Standards) Air-cooled 200 V/400 V Type (Option S only) (Option S only) RoHS HRSH090 Series How to Order HRSH 090 Cooling capacity Option 9.5 kW None With earth leakage breaker Cooling method With automatic fluid fill function Air-cooled refrigeration Applicable to deionized water piping...
Thermo-chiller Inverter Type (400 V type only) (UL Standards) Water-cooled 200 V/400 V Type (Option S only) (Option S only) RoHS HRSH090 Series How to Order HRSH 090 Option Cooling capacity None 11.0 kW Cooling method With earth leakage breaker Water-cooled refrigeration With automatic fluid fill function Applicable to deionized water piping...
Pump Capacity HRSH090--20/40- Caution Mechanical Seal Pump The pump used for the thermo-chiller HRSH090 series uses a Outlet mechanical seal with the fixed ring and rotary ring used for the shaft seal part. If foreign matter enter the gap between the...
HRSH090 Series Thermo-chiller Inverter Type Dimensions HRSH090-m-20/40 Ventilation air outlet Ventilation air inlet Circulating fluid fill port lid Serial communication (RS-485/RS-232C) connector Signal cable entry (Hole 40) Operation display panel D-sub female receptacle (Grommet with membrane) Option B Contact input/output ∗...
HRSH090 Series Inverter Type Recommended External Piping Flow External piping circuit is recommended as shown below. Thermo-chiller Facility water outlet (Water-cooled refrigeration) Facility water equipment Facility water inlet (Water-cooled refrigeration) Circulating fluid outlet User's equipment Circulating fluid return port Automatic fluid Fluid supply fill port (Option J)
HRSH090 Series Thermo-chiller Inverter Type Operation Display Panel List of Function The basic operation of this unit is controlled through the operation display panel on the front of the product. Function Outline Displays the current and set temperature of the 1 Main display circulating fluid, discharge pressure of the circulating fluid.
HRSH090 Series Inverter Type Communication Functions Contact Input/Output Item Specifications Connector type M3 terminal block Insulation method Photocoupler Rated input voltage 24 VDC Input signal Operating voltage range 21.6 to 26.4 VDC Rated input current 5 mA TYP Input impedance 4.7 kW Rated load voltage 48 VAC or less/30 VDC or less...
HRSH090 Series * Select the option when ordering Options the thermo-chiller because the option cannot be added after pur- chasing the unit. Option symbol With Earth Leakage Breaker HRSH090 20 B With earth leakage breaker A leakage breaker is built in to automatically stop the supply power when it has short-circuit, overcurrent or electrical leakage.
HRSH090 Series Optional Accessories q Piping Conversion Fitting This is a fitting to change the port from Rc to G or NPT. · Circulating fluid outlet, Circulating fluid return port Rc1 → NPT1 or G1 · Drain port Rc1/4 → NPT1/4 or G1/4 (It is not necessary to purchase this when pipe thread type F or N is selected in “How to Order”...
HRSH090 Series Optional Accessories e Electric Conductivity Control Set The set indicates and controls the electric conductivity of the circulating fluid. Refer to the Operation Manual for details. Part no. Applicable model HRS-DI007 HRSH090-ll-l (314) Measurement range of electric conductivity 2.0 to 48.0 mS/cm (Flying-out size) Circulating fluid Set range of electric conductivity target 5.0 to 45.0 mS/cm...
HRSH090 Series t Filter for Circulating Fluid Fill Port Prevents foreign matter from entering the tank when supplying the circulating fluid. Can be used just by fitting into the circulating fluid fill port. Tank lid Filter for circulating fluid fill port HRS-PF007 Filter for circulating fluid fill port Stainless steel 304,...
HRSH090 Series Optional Accessories u Wired Remote Controller When the wired remote controller is connected to the thermo-chiller, the operation start/stop setting or the set temperature can be changed from a place apart from the thermo-chiller. For details, refer to the Operation Manual. Wired Remote Controller HRS CV004 1 Accessories...
HRSH090 Series Cooling Capacity Calculation Required Cooling Capacity Calculation Example 1: When the heat generation amount in the user’s equipment is known. The heat generation amount can be determined based on the power consumption or output Q: Heat generation of the heat generating area — i.e. the area requiring cooling — within the user’s equipment. * amount I: Current User’s...
HRSH090 Series Cooling Capacity Calculation Required Cooling Capacity Calculation Example 3: When there is no heat generation, and when cooling the object below a certain temperature and period of time. Heat quantity by cooled substance (per unit time) Q : Unknown [W] ([J/s]) Example of current measurement units (Reference) Cooled substance : Water...
HRSH090 Series Specific Product Precautions 1 Be sure to read this before handling the products. Refer to page 383 for safety instructions and pages 384 to 387 for temperature control equipment precautions. Design Operating Environment/Storage Environment Warning Warning 1. This catalog shows the specifications of a single 1.
Page 26
HRSH090 Series Specific Product Precautions 2 Be sure to read this before handling the products. Refer to page 383 for safety instructions and pages 384 to 387 for temperature control equipment precautions. Transportation/Carriage/Movement Installation Warning Warning 1. This product is heavy. Pay attention to safety and 1.
Page 27
HRSH090 Series Specific Product Precautions 3 Be sure to read this before handling the products. Refer to page 383 for safety instructions and pages 384 to 387 for temperature control equipment precautions. Piping Circulating Fluid Caution Caution 1. Regarding the circulating fluid and facility water pipings, con- 5.
Page 28
HRSH090 Series Specific Product Precautions 4 Be sure to read this before handling the products. Refer to page 383 for safety instructions and pages 384 to 387 for temperature control equipment precautions. Facility Water Supply Operation Restart Time/Operation and Suspension Frequency Warning Caution 1.
Page 29
HRSH090 Series Specific Product Precautions 5 Be sure to read this before handling the products. Refer to page 383 for safety instructions and pages 384 to 387 for temperature control equipment precautions. Refrigerant with GWP reference Global warming potential (GWP) Revised Fluorocarbons Refrigerant Regulation (EU) No 517/2014...