Maintenance
Sensors
Sensor type Pt1000:
■
Boiler water temperature sensor
■
Buffer temperature sensor
■
Flow temperature sensor
■
Return temperature sensor
Connection
See chapter "Connection and wiring diagram".
Carrying out an actuator test
Note
An actuator test can only be carried out when the
boiler is cold.
If the actuator test is carried out for one mixer, all other
connected mixers remain in standard operation. Fol-
lowing the actuator test, the tested mixer reverts to
standard operation after 3 minutes.
The actuators are split into several categories, based
on their application:
■
Boiler actuators
Actuators for the corresponding mixer modules
■
Press the following keys:
1.
+
Simultaneously for approx. 4 s.
å
The "Service" menu appears.
2.
/
For "Actuator test".
|
~
The following boiler actuators can be switched, subject to system equipment level (not required during
commissioning):
Display
"Boiler pump On"
"Open boiler valve"
"Close boiler valve"
"Open buffer valve"
"Close buffer valve"
"Open prim air damper"
"Close prim air damper"
"Open sec air damper"
"Close sec air damper"
"Open central fault"
56
Flue gas temperature sensor
■
■
Outside temperature sensor
For heating circuit and DHW heating sensors,
refer to chapter "Extension kit".
3.
To confirm.
d
4.
/
For the required actuator category.
|
~
5.
To confirm.
d
6.
/
For the required actuator or relay output.
|
~
Note
The actuator test is terminated automati-
cally if no further input is made for 5 min.
7.
To confirm
d
8.
To terminate
d
9.
repeatedly, until the standard display is shown.
ä
The actuator test has been terminated.
Explanation
Test of fault alarm system connected on-site (if instal-
led).