Viessmann Vitoligno 250-S Installation And Service Instructions For Contractors page 46

Wood gasification boiler for logs with a length of 50 cm or 100 cm
Hide thumbs Also See for Vitoligno 250-S:
Table of Contents

Advertisement

Code 2
Heating group
(cont.)
Coding in the delivered condition
Screed drying
F1:0
Screed drying disabled
Boiler group
Coding
Coding in the delivered condition
Transfer heat from, temperature
10:100
From a boiler water temperature of
100 °C, heat is transferred via ena-
bled heating circuits. Which heat-
ing circuits are enabled for "Trans-
fer heat" is separately defined for
each heating circuit in code F3, in
the Heating group.
Minimum set system temperature
13:1
A minimum set system tempera-
ture can be set. Enable the func-
tion if the heating circuits are not
controlled by the boiler control unit.
O2 control active
5F:1
Control via flue gas oxygen con-
tent enabled.
Automatic system, O2 probe
F9:0
Lambda probe heating always
on
Only manual calibration of Lamb-
da probe, see chapter "Calibrat-
ing the Lambda probe"
O2 probe type
FF:0
Lambda probe used: Type LSM 11
Note
A LSM 11 Lambda probe is used
as standard in the Vitoligno 250-S.
46
Possible change
F1:1
Screed drying in accordance with
to
the selectable temperature:time pro-
F1:6
file (for more information, see chap-
ter "Screed drying").
Possible change
10:50
Setting range in °C
to
10:110
13:0
A minimum set system temperature
cannot be set.
5F:0
Control via flue gas oxygen content
disabled.
Emergency mode - adjust the air
damper position in the extended
menu.
F9:1
Automatic start of Lambda probe
heating
Calibration of Lambda probe only
manually
F9:2
Automatic start of Lambda probe
heating
Automatic calibration of Lambda
probe
FF:1
Lambda probe used: Type NGK
FF:2
Lambda probe used: Type LSU with
transducer