Viessmann Vitoligno 250-S Installation And Service Instructions For Contractors page 35

Wood gasification boiler for logs with a length of 50 cm or 100 cm
Hide thumbs Also See for Vitoligno 250-S:
Table of Contents

Advertisement

Calling up coding level 1
Codes are displayed as plain text.
Codes that have no function due to the heating sys-
tem equipment level or the setting of other codes are
not displayed.
Press the following keys:
1.
+
Simultaneously for approx. 4 s.
The "Service" menu appears.
2.
/
For "Code 1".
|
~
3.
To confirm.
d
Calling up coding level 2
At coding level 2, all codes are accessible, including
the codes at coding level 1.
Codes that have no function due to the heating sys-
tem equipment level or the setting of other codes are
not displayed.
Press the following keys:
1.
+
Simultaneously for approx. 4 s.
The "Service" menu appears.
2.
+
Simultaneously for approx. 4 s.
ä
"Code 2" appears in the "Service" menu.
4.
/
For the required group.
|
~
5.
To confirm.
d
6.
/
For the required coding address.
|
~
7.
To confirm.
d
8.
/
For the required value.
|
~
9.
To confirm.
d
"Adopted" appears briefly in the display.
10.
Exit the service menu.
ä
3.
/
For "Code 2".
|
~
4.
To confirm.
d
5.
/
For the required coding address.
|
~
6.
To confirm.
d
7.
/
For the required value.
|
~
8.
To confirm.
d
"Adopted" appears briefly in the display.
9.
Exit the service menu.
ä
Coding levels
35