Filling The Heating System; Checking All Connections On The Heating Water Side For Leaks - Viessmann Vitoligno 250-S Installation And Service Instructions For Contractors

Wood gasification boiler for logs with a length of 50 cm or 100 cm
Hide thumbs Also See for Vitoligno 250-S:
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Filling the heating system

Fill water
According to EN 1717 with DIN 1988-100, as a heat
transfer medium for DHW heating, the heating water
must meet fluid category ≤ 3. This requirement is met if
water of potable quality is used as heating water. For
example, if additives are used, the additive manufac-
turer must specify which category the treated heating
water comes under.
Total permissible hardness of the fill and top-up water
Total heating output
kW
50
50 to
200
>
200 to
600
>
600
>
Fig. 22
1. Check the pre-charge pressure of the diaphragm
expansion vessel.
If the pre-charge pressure is lower than the static
system pressure, top up with nitrogen. The pre-
charge pressure must be 0.1 to 0.2 bar (0.01 to
0.02 MPa) higher. If the pre-charge pressure is too
high, adjust it accordingly.

Checking all connections on the heating water side for leaks

24
Specific system volume
< 20 l/kW
3
3.0 mol/m
(16.8 °dH)
3
2.0 mol/m
(11.2 °dH)
1.5 mol/m
3
(8.4 °dH)
3
< 0.02 mol/m
(0.11 °dH)
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
Flush the heating system thoroughly before
filling.
Only use fill water of potable water quality.
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
20 l/kW to < 50 l/kW
3
2.0 mol/m
(11.2 °dH)
3
1.5 mol/m
(8.4 °dH)
0.02 mol/m
3
(0.11 °dH)
3
< 0.02 mol/m
(0.11 °dH)
2. Open the non-return valves.
3. Fill the heating system with water and vent the sys-
tem. The charge pressure must be 0.1 to 0.2 bar
(0.01 to 0.02 MPa) higher than the pre-charge
pressure of the diaphragm expansion vessel.
Permissible operating pressure: 3 bar (0.3 MPa)
Test pressure: 4 bar (0.4 MPa)
4. Mark the charge pressure at pressure gauge
5. Return the non-return valves to their operating
position.
50 l/kW
3
< 0.02 mol/m
(0.11 °dH)
3
< 0.02 mol/m
(0.11 °dH)
< 0.02 mol/m
3
(0.11 °dH)
3
< 0.02 mol/m
(0.11 °dH)
A
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sh20

Table of Contents