Viessmann Vitoligno 250-S Installation And Service Instructions For Contractors page 54

Wood gasification boiler for logs with a length of 50 cm or 100 cm
Hide thumbs Also See for Vitoligno 250-S:
Table of Contents

Advertisement

Troubleshooting
Fault display
(cont.)
Fault code dis-
System characteristics
played
63
No heating system control,
heating circuit 3
64
No DHW heating
65
No flow control, DHW heating Lead break, return tem-
90
Burner blocked
91
Boiler running with fixed air
damper setting
54
Cause
Lead break, flow tempera-
ture sensor, heating circuit
3
Lead break, cylinder tem-
perature sensor
perature sensor, DHW
heating
Fuel too damp
Lambda probe inaccu-
rate
Logs poorly charged
Lambda probe heavily
contaminated
Lambda probe faulty
Electronics fault
Measures
Check flow temperature sensor,
heating circuit 3.
Check cylinder temperature sen-
sor.
Check return temperature sensor,
DHW heating.
Use suitable dry fuel
Recalibrate Lambda probe
Acknowledge with OK
Recalibrate Lambda probe
Acknowledge with OK