Viessmann Vitoligno 250-S Installation And Service Instructions For Contractors page 21

Wood gasification boiler for logs with a length of 50 cm or 100 cm
Hide thumbs Also See for Vitoligno 250-S:
Table of Contents

Advertisement

Electrical connection, extension kit for...
1
1
1 (HC)
2
0
1 (HC)
2
1
1 (HC)
3
0
1 (HC)
Example for the S1 rotary selector settings of the
extension kits for:
2 heating circuits
1 DHW heating
A
Fig. 20
Rotary selector, extension kit, heating circuit 1 (set
A
value: 1)
Rotary selector, extension kit, heating circuit 2 (set
B
value: 3)
Rotary selector, extension kit, DHW heating (set
C
value: 5)
Other electrical connections
Make other electrical connections according to the
"System examples" document and the connection and
wiring diagrams from page 61.
Power supply
Regulations
Connect the power supply and implement all safety
measures (e.g. RCD circuit) in accordance with
IEC 60364-4-41, the connection requirements of your
local power supply utility and VDE or national regula-
tions.
Protect the power cable to the control unit with an
appropriate fuse/MCB.
(cont.)
3 (DHW)
3 (HC)
3 (HC)
3 (HC)
B
C
Mains isolator requirements
For combustion equipment to DIN VDE 0116, the
mains isolator installed on site must comply with the
requirements of DIN VDE 0116 "section 6" [or local
regulations].
Fit the mains isolator outside the installation room.
Ensure that it can isolate all non-earthed conductors
simultaneously with at least 3 mm contact separation.
Installation sequence
-
-
5 (DHW)
5 (HC)
21