Wiring

6
Wiring
6.1

General wiring guidelines

Please note:
}
Please refer to the technical details regarding the requirements of the supply voltages.
}
Safe electrical isolation must be ensured for the external power supplies that generate
the supply voltages. Failure to do so could result in electric shock.
}
The external power supplies must comply with the current applicable standard EN
60950-1, EN 61140, EN 50178 or EN 61558-1.
}
The maximum current load for the C-rail is 10 A. Please refer to the derating diagram.
}
Permitted infeed at the C-rail:
}
Earth the 0 V supply on the periphery supply or monitor each supply group for earth
faults.
}
The connection of the 0 V supply to the central earth bar or earth fault monitor must be
in accordance with the relevant national regulations (e.g. EN 60204-1, NFPA 79:17-7,
NEC: Article 250).
}
Minimum range for cable cross sections on connection terminals in mm
}
Use copper wiring.
}
To prevent contact welding, a fuse should be connected before the periphery supply in-
feed (see Technical details).
Operating Manual PSSu E F BSW(-T)
21372-EN-06
PE
0 V
Shield
- 30 VDC ... +30 VDC
- 48 VAC ... + 48 VAC
Power supply: 1.5 (AWG16) ... 2.5 (AWG12)
Functional earth: 1.5 (AWG16) ... 2.5 (AWG12)