Pilz PNOZ po3.2p Operating Manual
Pilz PNOZ po3.2p Operating Manual

Pilz PNOZ po3.2p Operating Manual

Expansion module
Hide thumbs Also See for PNOZ po3.2p:

Advertisement

Quick Links

PNOZ po3.2p
Safety relays
}
Operating Manual 20677-EN-06

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PNOZ po3.2p

  • Page 1 PNOZ po3.2p Safety relays Operating Manual 20677-EN-06...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Function Description Installation Wiring Preparing for operation Operation Status indicators Faults – Interference Dimensions in mm Technical details Safety characteristic data Supplementary data Service life graph Remove plug-in terminals Order reference EC declaration of conformity Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 4: Introduction

    PNOZ po3.2p Introduction Validity of documentation This documentation is valid for the product PNOZ po3.2p. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 5: Safety

    Safety Intended use The PNOZ po3.2p is an expansion module of the safety system PNOZpower. It may only be used with a base unit or a control module of the modular safety system PNOZpower. The expansion module meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1.
  • Page 6: Use Of Qualified Personnel

    Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 7: Unit Features

    The correct opening and closing of the safety device relays is tested automatically in each on-off cycle. Block diagram/terminal configuration 13 23 33 43 14 24 34 44 *Safe separation from non-marked area in accordance with EN 60947-1, 6 kV, basic insula- tion between all safety contacts. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 8: Function Description

    Fit the unit to a horizontal DIN rail. If other mounting positions are used, the switching capability values stated in the technical details cannot be maintained. There are 2 sockets on the rear of the PNOZ po3.2p. The base unit/control module and the expansion modules are connected using the jumpers supplied.
  • Page 9: Wiring

    Sufficient fuse protection must be provided on all output contacts with capacitive and in- ductive loads. Do not switch low currents using contacts that have been used previously with high cur- rents. Ensure the wiring and EMC requirements of IEC 60204-1 are met. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 10: Preparing For Operation

    Status indicators LEDs indicate the status and errors during operation: LED on POWER Supply voltage is present. CH.1 Safety contacts of channel 1 are closed. CH.2 Safety contacts of channel 2 are closed. FAULT Contact malfunction Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 11: Faults - Interference

    CCC, CE, EAC (Eurasian), TÜV, cULus Listed Electrical data Supply voltage Voltage 24 V Kind Power consumption 100 % Duty cycle Relay outputs Number of output contacts Safety contacts (N/O), instantaneous Utilisation category In accordance with the standard EN 60947-4-1 Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 12 Conv. therm. current with 2 contacts 16 A Conv. therm. current with 3 contacts 12 A Conv. therm. current with 4 contacts 10 A Times Switch-on delay With automatic start typ. 30 ms With automatic start max. 50 ms Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 13 0,5 - 4 mm², 20 - 10 AWG 1 core flexible Torque setting with screw terminals 0,5 Nm Dimensions Height 94 mm Width 90 mm Depth 135 mm Weight 490 g Where standards are undated, the 2014-07 latest editions shall apply. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 14: Safety Characteristic Data

    If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switching frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 15: Service Life Graph

    To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With DC con- tactors, use flywheel diodes for spark suppression. Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 16: Remove Plug-In Terminals

    The plug-in connection terminals should only be connected and disconnec- ted when the voltage is switched off. Order reference Product type Connection type Order No. PNOZ po3.2p Screw terminals 773 631 Operating Manual PNOZ po3.2p 20677-EN-06...
  • Page 17: Ec Declaration Of Conformity

    European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/support/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost- fildern, Germany Operating Manual PNOZ po3.2p...
  • Page 18 Back cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95446300 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland +41 62 88979-30 Mexico +43 1 7986263-0...

Table of Contents