NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the
installation and set-up instructions supplied with the heating appliance, as settings will differ from those
shown in this manual.
ACTUAL FIRING
RATE 5% ±
US GPH
0.50
0.60
0.75
0.80
0.95
ACTUAL FIRING
RATE 5% ±
US GPH
0.75
0.85
1.00
1.10
1.25
1.50
1.65
NOTE: The above set up charts are a starting point only. The burner and appliance must be properly set
up using proper combustion testing equipment.
Note: any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input
is corresponding the correct BTU/hr. or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the
appropriate installation codes (e.g. CSA B139 or NFPA #31).
C6501000 F3-F5 I-O manual Rev4_3

BURNER ADJUSTMENT TABLES

MODEL F3 BURNER SETUP CHART
NOZZLE
SIZE
PRESSURE
GPH
PSI
.40 x 60º/80º
160
.50 x 60º/80º
150
.60 x 60º/80º
150
.65 x 60º/80º
150
.75 x 60º/80º
160
MODEL F5 BURNER SETUP CHART
NOZZLE
PUMP
SIZE
PRESSURE
GPH
PSI
.60 x 60/ 80º
145
.65 x 60/ 80º
145
.85 x 60/ 80º
145
1.00 X 60/ 80°
145
1.10 x 60/ 80º
145
1.25 x 60/ 80º
145
1.35 X 60/ 80°
145
PUMP
TURBULATOR
BAR
SETTING
11.0
0.0
10.4
0.5
10.4
1.5
10.4
2.0
11.0
3.0
TURBULATOR
BAR
SETTING
10
0.0
10
0.5
10
1.0
10
2.0
10
2.5
10
3.0
10
4.0
AIR DAMPER
SETTING
2.3
2.7
3.4
3.6
4.3
AIR DAMPER
SETTING
2.25
2.5
2.75
3.0
3.5
4.25
6.0
15