RIELLO 40 SERIES MODELS 40 F3 & F5 EQUIPPED WITH ELECTRONIC AIR SHUTTER INSTALLATION & OPERATING MANUAL RESIDENTIAL OIL BURNERS NOTE: The settings in this manual are for retrofit applications. If this burner is being installed on a packaged unit (burner comes with the boiler or furnace), then follow the settings on the OEM page, as settings may differ.
TABLE OF CONTENTS TECHNICAL DATA - Model F3 ..................3 TECHNICAL DATA – Model F5 ..................4 OIL BURNER COMPONENT IDENTIFICATION............5 Serial Number Identification....................5 INITIAL SET-UP ......................5 ASSEMBLY OF AIR TUBE TO BURNER CHASSIS ............ 6 MOUNTING BURNER TO BOILER OR FURNACE............. 6 Method 1-Universal Mounting Flange ................
RIELLO 40 F3 TECHNICAL DATA DIMENSIONS MODEL F3 8 15/32 9 59/64 6 15/32 3 1/2 8 29/32 Inches E1: 10-inch long (254mm) tubes are also available. SPECIFICATIONS FUEL: NO heavier than # 2 FUEL OIL FIRING RATE: 0.50 to 0.95 US GPH EFFECTIVE OUTPUT: 70,000 to 133,000 BTU/h VOLTAGE (Single Phase):...
RIELLO 40 F5 TECHNICAL DATA DIMENSIONS MODEL F5 9 11/64 10 11/16 7 3/32 3 1/2 9 13/32 Inches E1: 10-inch long (254mm) tubes are also available. SPECIFICATIONS FUEL: NO heavier than # 2 FUEL OIL FIRING RATE: 0.75 to 1.65 US GPH EFFECTIVE OUTPUT: 105,000 to 231,000 BTU/h VOLTAGE (Single Phase):...
ASSEMBLY OF AIR TUBE TO BURNER CHASSIS The air tube and drawer assembly are shipped in a carton separate from the burner chassis. Choose the proper air tube length to obtain the tube insertion for the specific installation. A) Remove the AIR TUBE and BURNER CHASSIS from their respective cartons. B) Remove the DRAWER ASSEMBLY (1) from inside the AIR TUBE by loosening the screw (2).
METHOD 1 – UNIVERSAL MOUNTING FLANGE A) Insert the two BOLTS (1) into the UNIVERSAL MOUNTING FLANGE (10) from the flat side, ensuring the bolt heads are flush with the flat surface. Secure in place using two special CHROME NUTS (2) provided.
METHOD 3 – PEDESTAL MOUNT Secure the MOUNTING FLANGE to MOUNTING PEDESTAL using the hardware provided with the pedestal. Secure burner to MOUNTING FLANGE as in METHOD 1, item A, C and D. NOTE: It is suggested that the pedestal be anchored in position on the floor by installing brackets over the pedestal tube and securing brackets to the floor.
APPLICATION FIELD WIRING WIRING DIAGRAM SHOWN BELOW FOR STANDARD RIELLO 530 SE/C PRIMARY CONTROL BOX INSTALLATION NOTE: ELECTRONIC AIR SHUTTER REQUIRES A CONSTANT 120V POWER SUPPLY TO THE AUX TERMINAL, FAILURE TO PROVIDE THIS WILL RESULT IN NO BURNER OPERATION OR AIR SHUTTER WILL NOT CLOSE. R E C O M M E N D E D F I E L D W I R I N G F O R T Y P I C A L A P P L I C A T I O N S 1 2 0 V O P E R A T E D S Y S T E M S...
NOZZLE PLACEMENT A) Determine the proper firing rate for the boiler or furnace units, considering the specific application, and then use the Burner Setup charts on page 15 to select the proper nozzle and pump pressure to obtain the required input from the burner.
ELECTRODE SETTING IMPORTANT: THIS DIMENSIONS MUST BE OBSERVED AND VERIFIED. 5/32" - 4mm 13/64" 5/64" to 7/64" or 2 to2.5mm TURBULATOR SETTING A) Loosen NUT (1), and then turn SCREW (2) until the INDEX MARKER (3) is aligned with the correct index number as per the Burner Setup charts, or OEM specifications given with the appliance.
SINGLE LINE (GRAVITY FEED SYSTEM) A) The burner is shipped configured for use in single line applications. No changes to the oil pump are required for use in single line applications. NOTE: If the pump cover (1) is removed for any reason, be sure the O-ring (2), is properly seated in the pump cover (1) before re-attaching the pump cover to the pump housing.
line system, supply and return lines should be the same diameter and both should extend to the same depth inside the fuel tank. Be sure there are no air leaks or blockages in the piping system. Any obstructions in the return line will cause failure of the pump shaft seal. Do not exceed the pipe lengths indicated in the tables on page 10.
B) TWO LINE (LIFT SYSTEM) Turn off the main power source to the burner and remove the air tube cover. Shines a light source on the photocell (now visible where the air tube cover was removed), return power to the burner and activate the burner.
BURNER ADJUSTMENT TABLES NON-RETROFIT APPLICATIONS If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the installation and set-up instructions supplied with the heating appliance, as settings will differ from those shown in this manual.
AMULET INSTALLATION INSTRUCTIONS (Required on some models) The amulets provided have been selected by Riello to protect the combustion tube from hot exhaust gases and flame. This protection may be needed in applications where the combustion tube opening in the combustion chamber refractory is larger than the tube outside diameter.
RIELLO SPARE PARTS LIST revised November 6, 2002 • Indicates applicable model for each part. CODE DESCRIPTION CODE DESCRIPTION 3007232 • Burner Back Cover C7001029 • • Primary Control 3007233 • Burner Back Cover 3005854 • • Semi Flange (2 Required) 3006992 •...
assistance is required. Please complete this form, fax it or mail it at the address/fax above, or send an e-mail with the information listed below to: techservices@riellocanada.com INSTALLATION PRECAUTIONS AIR FOR COMBUSTION Do not install burner in room with insufficient air for combustion. Be sure there is an adequate air supply for combustion if the boiler/furnace room is enclosed.