Electrode Setting; Turbulator Setting; Pump Connections And Port Identification - Riello Burners RIELLO 40 Series Installation & Operating Manual

Hide thumbs Also See for RIELLO 40 Series:
Table of Contents

Advertisement

A) Loosen NUT (1), and then turn SCREW (2) until the INDEX MARKER (3) is aligned with the correct
index number as per the Burner Setup charts, or OEM specifications given with the appliance.
B) Retighten the RETAINING NUT (1).
NOTE: OEM specifications take priority over retrofit
specifications shown in this manual.
MODEL F3 NOTE: Zero and four are scale indicators only
From left to right the first line is 3 and the last line 0.
MODEL F5: Same as above, except, scale indicators are 0
and 4.

PUMP CONNECTIONS AND PORT IDENTIFICATION

This burner is shipped with the oil pump set to operate on a single line system. To operate on a two-line system the by-
pass plug must be installed.
WARNING: Do not operate a single line system with the by-pass plug installed. Operating a single line system with the
by-pass plug installed will result in damage to the pump shaft seal.
NOTE: Pump pressure must be set at time of burner start-up. A pressure gauge is attached to the PRESSURE PORT (7)
for pressure readings. Two PIPE CONNECTORS (4) are supplied with the burner for connection to either a single or
two-line system. Also supplied are two ADAPTORS (3), two female ¼" NPT, to adapt oil lines to burner pipe
connectors. All pump port threads are British Parallel Thread design. Direct connection of NPT threads to the pump will
damage the pump body.
Riello manometers and vacuum gauges do not require any adapters, and can be safely connected to the pump ports. An
NPT (metric) adapter must be used when connecting other gauge models.
1
2
3
C6501000 F3-F5 I-O manual Rev4_3

ELECTRODE SETTING

IMPORTANT: THIS DIMENSIONS MUST BE OBSERVED AND VERIFIED.
5/32" - 4mm
5/64" to 7/64" or 2 to2.5mm

TURBULATOR SETTING

6
5
8
4
4
12
11
PUMP LEGEND
1. PUMP COVER
10
2. PUMP COVER O-RING
3. BSPP TO NPT ADAPTERS
V
7
4. SUPPLY AND RETURN OIL LINES
RIELLO
5. RETURN PORT BY PASS SCREW
P
6. NOZZLE PORT - PUMP OULET TO NOZZLE
7. PUMP PRESSURE PORT AND BLEEDER PORT
8. PUMP SUPPLY PORT
9. PUMP RETURN PORT
10. PUMP PRESSURE REGULATING SCREW
9
11. VACUUM PORT
12. PUMP VALVE STEM
13/64"
5mm
3
4
0
2
0
1
11