Connection diagram
To prevent restart at fault occurrence, connect terminals So (SO) and SOC to the reset button, which are the feedback input
terminals of the safety relay module.
RESET
Emergency
stop button
/ Safety programmable controller
Safety stop function operation
Internal
Input terminal
Input
safety
circuit
power
S1
status
OFF
-
-
Normal
ON
Normal
ON
Normal
OFF
Normal
OFF
ON
Fault
ON
Fault
ON
Fault
OFF
Fault
OFF

ON: The transistor is conducted. OFF: The transistor is not conducted.

When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter. (In the initial status,
terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)

If any of the protective functions shown in the following table is activated, terminal So (SO) and the SAFE output signal turn OFF.
Fault record
Option fault
Communication option fault
Parameter storage device fault
Retry count excess
Parameter storage device fault
Operation panel power supply short circuit

If the internal safety circuit is operated normally, terminal So (SO) and the SAFE output signal remain ON until E.SAF is displayed, and terminal
So (SO) and the SAFE output signal turn OFF when E.SAF is displayed.

SA is displayed when terminals S1 and S2 are identified as OFF due to the internal safety circuit failure.

If another fault occurs at the same time as E.SAF, the other fault can be displayed.

If another warning occurs at the same time as SA, the other warning can be displayed.

For the SAFE signal, refer to the following table and use any of Pr.190 to Pr.196 (output terminal function selection) to assign the function to
the output terminal. The ON/OFF state of the output signal is the one for the positive logic. The ON and OFF are reversed for the negative logic.
Output
signal
SAFE

The use of SAFE signal has not been certified for compliance with safety standards.
For more details, refer to the Safety stop function instruction manual. (A PDF copy can be found in the enclosed CD-ROM.
For how to use this CD-ROM, refer to
So (SO)
SOC
+24 V
PC
Fuse
24 VDC
S2
S1
SIC
SD
Safety relay module
Output
,


terminal
S2
So (SO)
-
OFF
OFF
ON
ON

OFF
OFF
OFF

OFF
ON
OFF

OFF
OFF
ON

ON
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
Operation panel
indication
E.OPT
E.OP1
E.PE
E.RET
E.PE2
E.CTE
Pr.190 to Pr.196 setting
Positive logic
Negative logic
80
180
page
111.)
Inverter
Logic
ASIC
CPU
Output
Inverter running
signal
,


status
SAFE
Output shutoff (Safe state) Not displayed
Operation enabled
Output shutoff (Safe state) Displayed


Output shutoff (Safe state) Displayed

Output shutoff (Safe state) Not displayed
Output shutoff (Safe state) Displayed
Output shutoff (Safe state) Displayed
Output shutoff (Safe state) Displayed
Output shutoff (Safe state) Displayed
Fault record
24 VDC power fault
Safety circuit fault
Overspeed occurrence
CPU fault
Internal circuit fault
INSTALLATION AND WIRING
Control circuit
R/L1 S/L2 T/L3
IGBTs
Gate
Gate
Driver
Driver
G
G
U V W
M
Operation panel
indication
E.SAF
SA

Not displayed
Not displayed
Not displayed
Displayed
Displayed
Displayed
Not displayed
Displayed
Displayed
Displayed
Operation panel
indication
E.P24
E.SAF
E.OS
E.CPU
E.5 to E.7
E.13


2
47