CS signal command source selection
The CS signal can be used via communication.
 Extended setting range of automatic restart after instantaneous
power failure selection
• In the Network operation mode, the command source of the CS signal can be selected according to the setting in Pr.162
Automatic restart after instantaneous power failure selection.
Pr.
Name
Automatic restart after
162
instantaneous power
A700
failure selection
*1
The same operation is performed for the both settings.
 Automatic restart after instantaneous power failure selection (Pr.162)
*1
Pr.162 Setting
[][][]0
[][][]1
Automatic restart after instantaneous power failure selection
[][][]2
[][][]3
[][]0[]
Restart timing
[][]1[]
0[][][]
CS signal command source selection under Network operation mode
1[][][]
*1
Zero of the most significant digit is not displayed.
*2
The setting value of Pr.162 and restart operation under each control method are as follows.
Pr.162
V/F control, Advanced magnetic flux vector control
Setting
[][][]0
Frequency search
[][][]1
Reduced voltage start
[][][]2
Frequency search
[][][]3
Frequency search (reduced impact restart)
Initial value
Setting range
*1
0 (2)
,
*1
1000 (1002)
1, 1001
3, 1003
0
*1
10, (12)
, 1010
*1
(1012)
11, 1011
13, 1013
Frequency search for a PM motor
Frequency search only performed at the first start
Reduced voltage start only at the first start
(no frequency search)
Frequency search only performed at the first start (reduced impact
restart)
Frequency search at every start
Reduced voltage start at every start (no frequency search)
Frequency search at every start (reduced impact restart)
Description
*2
PM motor control
3
Description
Restart only at the first start
Restart at every start
Always External
NET (Pr.338="0")
External (Pr.338="1")
BCN-C22005-865