DSE4610 & DSE4620 Operator Manual
Document Number: 057-200
Author: Tony Manton
DSE4610 & DSE4620 Operator Manual ISSUE 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DSE4610 and is the answer not in the manual?

Questions and answers

Андрей
February 11, 2025

Добрый день Не могу запустить ДЭС атлас копии, на панеле стоп индикатор мигает и ошибка в правом верхнем углу не уходит. Подскажите что это может быть и как обойти данную неисправность пожалуйста... За разумное вознаграждение)) Так же есть контроллер 4520 , на нëм после редактирования параметров перестали работать кнопки auto и start, а стоп горит ровным счетом((( обе ДЭС не могу завести..... Прошу помощи

1 comments:
Mr. Anderson
February 12, 2025

The flashing stop indicator and error message on the DSE4610 panel indicate a fault condition, such as an engine failure or corrupted configuration file. The issue can be resolved by checking the LCD display for specific fault messages, verifying configuration settings, and ensuring that the engine and system parameters are correctly set.

The auto and start buttons on the DSE4620 may not work after parameter editing due to a configuration issue or file corruption. This can be resolved by verifying the configuration file integrity, reloading the correct settings, and ensuring that the controller is properly set up for operation.

This answer is automatically generated

Subscribe to Our Youtube Channel

Summary of Contents for DSE DSE4610

  • Page 1 DEEP SEA ELECTRONICS PLC DSE4610 & DSE4620 Operator Manual Document Number: 057-200 Author: Tony Manton DSE4610 & DSE4620 Operator Manual ISSUE 1...
  • Page 2 Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective companies.
  • Page 3: Table Of Contents

    DSE4610 & DSE4620 Operator Manual TABLE OF CONTENTS Section Page BIBLIOGRAPHY ....................6 INSTALLATION INSTRUCTIONS .................. 6 TRAINING GUIDES ......................6 MANUALS ........................6 THIRD PARTY DOCUMENTS ..................6 INTRODUCTION ....................7 SPECIFICATIONS .................... 8 SHORT NAMES ......................8 OPERATING TEMPERATURE ..................8 REQUIREMENTS FOR UL CERTIFICATION ..............
  • Page 4 4.1.6 PC CONFIGURATION INTERFACE CONNECTOR ..........29 TYPICAL WIRING DIAGRAM ..................30 4.2.1 DSE4610 TYPICAL WIRING DIAGRAM (3 PHASE 4 WIRE) ......... 31 4.2.2 DSE4620 TYPICAL WIRING DIAGRAM (3 PHASE 4 WIRE) ......... 32 ALTERNATE TOPOLOGY WIRING DIAGRAMS ............33 4.3.1...
  • Page 5 LOADING ........................81 ALARMS ........................82 INSTRUMENTS ......................82 MISCELLANEOUS ....................... 83 MAINTENANCE, SPARES, REPAIR AND SERVICING ......84 10.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE ......84 10.1.1 PACK OF PLUGS ....................84 10.1.2 INDIVIDUAL PLUGS ....................84 10.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE .........
  • Page 6: Bibliography

    Bibliography 1 BIBLIOGRAPHY This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website: www.deepseaplc.com 1.1 INSTALLATION INSTRUCTIONS Installation instructions are supplied with the product in the box and are intended as a ‘quick start’...
  • Page 7: Introduction

    Introduction 2 INTRODUCTION This document details the installation and operation requirements of the DSE4610 & DSE4620 modules, part of the DSEGenset® range of products. The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes.
  • Page 8: Specifications

    Short Name Description DSE4000,DSE4xxx All modules in the DSE4000 range. DSE4600,DSE46xx All modules in the DSE4600 range. DSE4610 DSE4610 module/controller DSE4620 DSE4620 module/controller 3.2 OPERATING TEMPERATURE Module Description DSE46xx -30ºC to +70ºC (-40ºC to +70ºC for variants fitted with display heaters) 3.3 REQUIREMENTS FOR UL CERTIFICATION...
  • Page 9: Terminal Specification

    Specification 3.4 TERMINAL SPECIFICATION NOTE: For purchasing additional connector plugs from DSE, please see the section entitled Maintenance, Spares, Repair and Servicing elsewhere in this document. Two part connector. Male part fitted to • module Female part supplied in •...
  • Page 10: Voltage & Frequency Sensing

    Specification 3.6 VOLTAGE & FREQUENCY SENSING Measurement Type True RMS conversion Sample Rate 5kHz or better Harmonics Up to 11 or better Input Impedance 300kΩ phase to neutral to 415V AC (absolute maximum) (minimum required for sensing frequency Phase To Neutral Suitable for 345V nominal (±20% for under/overvoltage detection) to 720V AC...
  • Page 11: Va Rating Of The Cts

    CT is approximately 7VA. CT’s required in this instance is at least 7.5VA (7+0.5). NOTE: Details for 4mm² cables are shown for reference only. The connectors on the DSE modules are only suitable for cables up to 2.5mm².
  • Page 12: Ct Polarity

    3.7.3 CT PHASING Take particular care that the CTs are connected to the correct phases. For instance, ensure that the CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for phase 1.
  • Page 13: Inputs

    Specification 3.8 INPUTS 3.8.1 DIGITAL INPUTS 4 configurable digital inputs Number (7 when Analogue Inputs are configured as digital inputs) Arrangement Contact between terminal and ground Low Level Threshold 3.2V minimum High Level Threshold 8.1V maximum Maximum Input Voltage +60V DC with respect to plant supply negative Minimum Input Voltage -24V DC with respect to plant supply negative Contact Wetting Current...
  • Page 14: Fuel Level Sensor

    It is this drop in voltage that triggers the charge failure alarm. The level at which this operates and whether this triggers a warning or shutdown alarm is configurable using the DSE Configuration Suite Software.
  • Page 15: Magnetic Pickup

    Specification 3.8.4 MAGNETIC PICKUP Type Single ended input, capacitive coupled Minimum Voltage 0.5V RMS Max Common Mode Voltage ±2V Maximum Voltage Clamped to ±70V by transient suppressers, dissipation not to exceed 1W. Maximum Frequency 10,000Hz Resolution 6.25 RPM Accuracy ±25 RPM Flywheel Teeth 10 to 500 3.9 OUTPUTS...
  • Page 16: Usb Port

    The USB port is provided to give a simple means of connection between a PC and the controller. Using the DSE Configuration Suite Software, the operator is then able to control the module, starting or stopping the generator, selecting operating modes, etc.
  • Page 17: Adding An External Sounder

    Specification 3.11 ADDING AN EXTERNAL SOUNDER Should an external alarm or indicator be required, this can be achieved by using the DSE Configuration Suite PC software to configure an auxiliary output for “Audible Alarm”, and by configuring an auxiliary input for “Alarm Mute” (if required).
  • Page 18: Dimensions And Mounting

    Specification 3.13 DIMENSIONS AND MOUNTING 3.13.1 DIMENSIONS 140.0mm x 113mm x 43mm (5.5” x 4.4” x 1.7”) 3.13.2 PANEL CUTOUT 118mm x 92mm (4.6” x 3.6”) 3.13.3 WEIGHT 0.16kg (0.35lb)
  • Page 19: Fixing Clips

    Specification 3.13.4 FIXING CLIPS The module is held into the panel fascia using the supplied fixing clips. Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding • from the clip. • Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case. Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of •...
  • Page 20: Silicon Sealing Gasket

    Specification 3.13.5 SILICON SEALING GASKET NOTE: For purchasing an additional silicon gasket from DSE, please see the section entitled Maintenance, Spares, Repair and Servicing elsewhere in this document. The optional silicon gasket provides improved sealing between module and the panel fascia.
  • Page 21: Applicable Standards

    Specification 3.13.6 APPLICABLE STANDARDS This document conforms to BS4884-1 1992 Specification for BS 4884-1 presentation of essential information. BS 4884-2 This document conforms to BS4884-2 1993 Guide to content BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation BS EN 60068-2-1 -30°C (-22°F) (Minimum temperature)
  • Page 22 Specification IEEE C37.2 Continued (Standard Electrical 50 – Instantaneous Overcurrent Relay Power System Device 52 – AC Circuit Breaker Function Numbers and Contact Designations) 53 – Exciter Or DC Generator Relay 54 – Turning Gear Engaging Device 59AC – AC Overvoltage Relay 59DC –...
  • Page 23: Enclosure Classifications

    Specification 3.13.7 ENCLOSURE CLASSIFICATIONS 3.13.7.1 IP CLASSIFICATIONS The modules specification under BS EN 60529 Degrees of protection provided by enclosures IP65 (Front of module when module is installed into the control panel with the optional sealing gasket). IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) First Digit Second Digit Protection against contact and ingress of solid objects...
  • Page 24: Nema Classifications

    Specification 3.13.7.2 NEMA CLASSIFICATIONS THE MODULES NEMA RATING (APPROXIMATE) 12 (Front of module when module is installed into the control panel with the optional sealing gasket). 2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) NOTE: There is no direct equivalence between IP / NEMA ratings.
  • Page 25: Installation

    Installation – Terminal Description 4 INSTALLATION The module is designed to be mounted on the panel fascia. For dimension and mounting details, see the section entitled Specification, Dimension and mounting elsewhere in this document. 4.1 TERMINAL DESCRIPTION To aid user connection, icons are used on the rear of the module to help identify terminal functions. An example of this is shown below.
  • Page 26: Dc Supply, Fuel And Start Outputs, Outputs C, D, E & F

    Plant Supply Positive from terminal 2. 2 Amp rated. AWG 18 1.0mm² DC Output F Plant Supply Positive from terminal 2. 2 Amp rated. AWG 18 NOTE: Terminals 8 & 9 are not fitted to DSE4610 controller. 4.1.2 ANALOGUE SENSOR Cable Description Notes Size 0.5mm²...
  • Page 27: Configurable Digital Inputs & Magnetic Pickup

    Connect to Magnetic Pickup device AWG 20 Magnetic Pickup Screen Do not connect the other end to earth! NOTE: For further details of module configuration, refer to DSE Publication: 057-201 DSE46xx Configuration Software Manual. 4.1.4 GENERATOR / MAINS VOLTAGE & FREQUENCY SENSING...
  • Page 28: Geneator Current Transformers

    L is the primary of the CT that ‘points’ towards the Load s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring s2 is the secondary of the CT that should be commoned with the s2 connections of all the other CTs and connected to the CT common terminal of the module.
  • Page 29: Pc Configuration Interface Connector

    CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the recommended number of USB devices to the PC. For further information, consult your PC supplier. NOTE: For further details of module configuration, refer to DSE Publication: 057-201 DSE46xx Configuration Software Manual.
  • Page 30: Typical Wiring Diagram

    Genset manufacturers and panel builders may use these diagrams as a starting point; however, you are referred to the completed system diagram provided by your system manufacturer for complete wiring detail. Further wiring suggestions are available in the following DSE publications, available at www.deepseaplc.com to website members.
  • Page 31: Dse4610 Typical Wiring Diagram (3 Phase 4 Wire)

    Installation – Typical Wiring Diagrams 4.2.1 DSE4610 TYPICAL WIRING DIAGRAM (3 PHASE 4 WIRE) NOTE: Terminals 29-32 are not fitted on the DSE46xx-01 variant.
  • Page 32: Dse4620 Typical Wiring Diagram (3 Phase 4 Wire)

    Installation – Typical Wiring Diagrams 4.2.2 DSE4620 TYPICAL WIRING DIAGRAM (3 PHASE 4 WIRE) NOTE: Terminals 29-32 are not fitted on the DSE46xx-01 variant.
  • Page 33: Alternate Topology Wiring Diagrams

    Installation – Alternate Topology Wiring Diagrams 4.3 ALTERNATE TOPOLOGY WIRING DIAGRAMS 4.3.1 GENERATOR...
  • Page 34: Mains (4620 Only)

    Installation – Typical Wiring Diagrams 4.3.2 MAINS (4620 ONLY)
  • Page 35: Earth Systems

    (the battery negative connects to Earth) 4.4.2 POSITIVE EARTH When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the following points must be followed: Follow the typical wiring diagram as normal for all sections EXCEPT the earth points •...
  • Page 36: Description Of Controls

    Description Of Controls 5 DESCRIPTION OF CONTROLS NOTE: The following descriptions detail the sequences followed by a module containing the standard ‘factory configuration’. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field. Control of the module is via push buttons mounted on the front of the module with Stop/Reset Mode , Auto Mode...
  • Page 37: Control Push-Buttons

    Description Of Controls 5.1 CONTROL PUSH-BUTTONS Icon Description Stop / Reset Mode This button places the module into its Stop/Reset Mode . This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and the module is put into Stop mode, the module will automatically instruct the generator to unload (‘Close Generator’...
  • Page 38: Module Display

    The module’s display contains the following sections. Description of each section can be viewed in the sub sections. NOTE: Depending upon the module’s configuration, some display screens may be disabled. For further details of module configuration, refer to DSE Publication: 057-201 DSE46xx Configuration Software Manual. Inst.
  • Page 39: Instrumentation Icons

    Viewing The Instrument Pages 5.2.1 INSTRUMENTATION ICONS When viewing instrumentation pages, an icon is displayed in the Inst. Icon section to indicate what section is currently being displayed. Icon Details The default home page which displays generator voltage and mains voltage (DSE4620 only) Generator voltage and frequency instrumentation screen Mains voltage and frequency instrumentation screen (DSE4620 only) Generator current instrumentation screen...
  • Page 40: Active Configuration

    Viewing The Instrument Pages 5.2.2 ACTIVE CONFIGURATION An icon is displayed in the Active Config section to indicate the active configuration within the currently selected within the controller. Icon Details Appears when the main configuration is selected. Appears when the alternative configuration is selected. 5.2.3 FRONT PANEL EDITOR (FPE) / AUTO RUN ICON NOTE: For further details about the Front Panel Editor, see the section entitled ‘Front Panel Editor’...
  • Page 41: Load Switching Icon

    Viewing The Instrument Pages 5.2.5 LOAD SWITCHING ICON An icon is displayed in the Load Switching Icon section to indicate the current operation status of the controller. Icon Details Appears when the generator is at rest or not available and when the generator breaker is open.
  • Page 42: Alarm Icons (Protections)

    Example: If the DSE controller was sensing a charge alternator failure alarm, delay over current alarm and a AC under voltage alarm at the same time, it would cycle through all of the icons to show this.
  • Page 43: Warning Alarm Icons

    By default, warning alarms are self-resetting when the fault condition is removed. However enabling ‘all warnings are latched’ will cause warning alarms to latch until reset manually. This is enabled using the DSE Configuration Suite in conjunction with a compatible PC. Icon...
  • Page 44: Electrical Trip Alarm Icons

    Open Circuit Loss Of Mag. Pickup The speed signal from the magnetic pickup is not being received by the DSE controller. Signal 5.2.7.2 ELECTRICAL TRIP ALARM ICONS Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module de-energises all the ‘Delayed Load Output’...
  • Page 45: Shutdown Alarm Icons

    Viewing The Instrument Pages 5.2.7.3 SHUTDOWN ALARM ICONS Shutdown alarms are latching and immediately stop the Generator. On initiation of the shutdown condition the module de-energises all the ‘Delayed Load Output’ and the ‘Close Gen Output’ outputs to remove the load from the generator. Once this has occurred, the module shuts the generator set down immediately to prevent further damage.
  • Page 46 Maintenance due for fuel filter. Maintenance Alarm Magnetic Pickup Magnetic pickup sensor has been detected as being open circuit. Open Circuit The speed signal from the magnetic pickup is not being received by Loss Of Mag. Pickup the DSE controller. Signal...
  • Page 47: Viewing The Instrument

    Viewing The Instrument Pages 5.3 VIEWING THE INSTRUMENT PAGES 5.3.1 NAVIGATION MENU To enter the navigation menu, press both the (up) and (down) buttons simultaneously. To select the required icon, press the (up) button to cycle right or the (down) button to cycle left until the desired instrumentation section is reached.
  • Page 48: General Navigation

    (Page Delay Timer), the module reverts back to the Home ) page. The Page Delay Timer is configurable using the DSE Configuration Suite Software or by using the Front Panel Editor. NOTE: For further details of module configuration, refer to DSE Publication: 057-201...
  • Page 49: Home

    Viewing The Instrument Pages 5.3.3 HOME This is the page that is displayed when no other page has been selected and is automatically displayed after a period of inactivity (Page Delay Timer) of the module facia buttons. It also contains the voltage reading of the generator and mains that is measured from the module’s voltage inputs.
  • Page 50: Mains (Dse4620 Only)

    Viewing The Instrument Pages 5.3.5 MAINS (DSE4620 ONLY) These pages contain electrical values of the mains, measured or derived from the module’s voltage inputs. Mains Voltage (ph-N) • Mains Voltage (ph-ph) • Mains Frequency • 5.3.6 LOAD These pages contain electrical values of the load, measured or derived from the module’s voltage and current inputs.
  • Page 51: Engine

    Viewing The Instrument Pages 5.3.7 ENGINE These pages contain instrumentation gathered about the engine measured or derived from the module’s inputs. 1500 Engine Speed • Engine Run Time • Engine Battery Volts • Engine Coolant Temperature • Engine Oil Pressure •...
  • Page 52: Event Log

    Viewing The Instrument Pages 5.3.9 EVENT LOG This module’s event log contains a list of the last 15 record electrical trip or shutdown events and the engine hours at which they occurred. Once the log is full, any subsequent electrical trip or shutdown alarms overwrites the oldest entry in the log.
  • Page 53: Operation

    Operation 6 OPERATION NOTE: The following descriptions detail the sequences followed by a module containing the standard ‘factory configuration’. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field. 6.1 QUICKSTART GUIDE This section provides a quick start guide to the module’s operation.
  • Page 54: Stopping The Engine

    Operation 6.1.2 STOPPING THE ENGINE Select Stop/Reset mode. The generator is stopped. NOTE: For further details, see the section entitled ‘OPERATION’ elsewhere in this manual.
  • Page 55: Stop/Reset Mode

    Oil pressure sensor must indicate low oil pressure • When the engine has stopped, it is possible to send configuration files to the module from DSE Configuration Suite PC software and to enter the Front Panel Editor to change parameters.
  • Page 56: Automatic Mode

    Operation 6.3 AUTOMATIC MODE NOTE: If a digital input configured to external panel lock is active, changing module modes is not possible. Viewing the instruments and event logs is NOT affected by panel lock. Auto Mode is activated by pressing the Auto Mode button.
  • Page 57: Stopping Sequence

    Operation 6.3.4 STOPPING SEQUENCE The return delay timer operates to ensure that the starting request has been permanently removed and isn’t just a short term removal. Should another start request be made during the cooling down period, the set returns on load. If there are no starting requests at the end of the return delay timer, the load is removed from the generator to the mains supply and the cooling timer is initiated.
  • Page 58: Manual/Start Mode

    Protected Start Mode setting in the DSE Configuration Suite Software NOTE: For further details of module configuration, refer to DSE Publication: 057-201 DSE46xx Configuration Software Manual. 6.4.2 STARTING SEQUENCE NOTE: There is no start delay in this mode of operation.
  • Page 59: Engine Running

    Operation 6.4.3 ENGINE RUNNING Once the engine is running and all starting timers have expired, the animated Engine Running icon is displayed In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made. A loading request can come from a number of sources. Activation of an auxiliary input that has been configured to Remote Start On Load or Auxiliary •...
  • Page 60: Maintenance Alarm

    Alarm x, where x is the type of maintenance alarm (Air, Fuel or Oil). • Pressing the maintenance reset button in the DSE Configuration Suite, Maintenance section. • Pressing and holding the Stop/Reset Mode button for 10 seconds on the desired Maintenance Alarm status page.
  • Page 61: Scheduler

    Up to 8 scheduled start/stop sequences can be configured to repeat on a 7-day or 28-day cycle. Scheduled runs may be on load or off load depending upon module configuration. Example Screen capture from DSE Configuration Suite Software showing the configuration of the Exercise Scheduler.
  • Page 62: Front Panel Configuration

    This configuration mode allows the operator to fully configure the module through its display without the use of the DSE Configuration Suite PC Software. Use the module’s facia buttons to traverse the menu and make value changes to the parameters: Next Section (101→201→301)
  • Page 63: Accessing The Front Panel Configuration Editor

    PIN code set, this has been affected by your generator supplier who should be contacted if you require the code. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to the DSE factory to have the module’s code removed. A charge will be made for this procedure.
  • Page 64: Adjustable Parameters

    Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Module (Page 1) Contrast 0 (%)
  • Page 65: Input Settings

    Front Panel Configuration 7.2.2 INPUT SETTINGS Configuration Parameters – Inputs (Page 3) Digital Input A Source 0 (Input Source) Digital Input A Polarity 0 (Polarity) Digital Input A Action (If Source = User Config) 0 (Action) Digital Input A Arming (If Source = User Config) 0 (Arming) Digital Input A Activation Delay (If Source = User Config) Digital Input B Source...
  • Page 66: Output Settings

    Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Outputs (Page 4) Digital Output A Source...
  • Page 67: Generator Settings

    Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Generator (Page 6) Alternator Fitted On (1), Off (0)
  • Page 68: Mains Settings

    Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Mains (Page 7) AC System 0 (AC System)
  • Page 69: Engine Settings

    Front Panel Configuration 7.2.7 ENGINE SETTINGS Configuration Parameters – Engine (Page 8) Start Attempts Over Speed Overshoot Over Speed Delay Gas Choke Timer (Gas Engine Only) Gas On Delay (Gas Engine Only) Gas Ignition Off Delay (Gas Engine Only) Crank Disconnect On Oil Pressure Enable On (1), Off (0) Check Oil Pressure Prior To Starting On (1), Off (0)
  • Page 70: Analogue Inputs Settings

    Front Panel Configuration 7.2.8 ANALOGUE INPUTS SETTINGS Configuration Parameters – Analogue Input Settings (Page 9) Analogue Input A Senor Type 0 (Sensor Type) Analogue Input A Sensor Selection 0 (Pressure Sensor List) Low Oil Pressure Enable On (1), Off (0) Low Oil Pressure Trip 0 Bar Oil Pressure Sender Open Circuit...
  • Page 71: Scheduler Settings

    Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Scheduler (Page 10) 1001 Enable Scheduler...
  • Page 72: Maintenance Alarm Settings

    Front Panel Configuration 7.2.11 MAINTENANCE ALARM SETTINGS Configuration Parameters – Maintenance Alarms (Page 12) 1201 Oil Maintenance Alarm Enable On (1), Off (0) 1202 Oil Maintenance Alarm Action 0 (Action) 1203 Oil Maintenance Alarm Engine Hours 1204 Air Maintenance Alarm Enable On (1), Off (0) 1205 Air Maintenance Alarm Action...
  • Page 73 Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only Configuration Parameters – Alternate Configuration (Page 20) 2024 CT Primary...
  • Page 74: Selectable Parameter Settings

    7.3.1 INPUT SOURCES Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only INPUT SOURCES User Configured Alarm Mute...
  • Page 75: Output Sources

    7.3.2 OUTPUT SOURCES Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only OUTPUT SOURCES Not Used Air Flap Relay...
  • Page 76 Functionality in all DSE4610 & DSE4620 variants Functionality in all DSE4620 variants Functionality in DSE4610 & DSE4620 current sensing variants only Functionality in DSE4610 & DSE4620 RT & RTH variants only OUTPUT SOURCES Oil Pressure Sender Open Circuit Open Gen Output...
  • Page 77: Alarm Action

    Front Panel Configuration 7.3.3 ALARM ACTION ALARM ACTION Index Action Electrical Trip Shutdown Warning 7.3.4 FLEXIBLE SENSOR ALARM ACTION FLEXIBLE SENSOR ALARM ACTION Index Action None Shutdown Electrical Trip 7.3.5 POWER UP MODE POWER UP MODE Index Mode Stop Manual Auto 7.3.6 SENSOR TYPE SENSOR TYPE...
  • Page 78: Digital Input Alarm Arming

    Front Panel Configuration 7.3.8 DIGITAL INPUT ALARM ARMING DIGITAL INPUT ALARM ARMING Index Arming Always From Safety On From Starting Never 7.3.9 DIGITAL INPUT POLARITY DIGITAL INPUT POLARITY Index Polarity Close to Activate Open to Activate 7.3.10 DIGITAL OUTPUT POLARITY OUTPUT POLARITY Index Polarity...
  • Page 79: Pressure Sensor List

    Front Panel Configuration 7.3.12 PRESSURE SENSOR LIST PRESSURE SENSOR LIST Index Type Not used Dig Closed for Alarm Dig Open for Alarm VDO 5 Bar VDO 10 Bar Datcon 5 Bar Datcon 10 Bar Datcon 7 Bar Murphy 7 Bar CMB812 Veglia User Defined...
  • Page 80: Commissioning

    NOTE: If Emergency Stop feature is not required, link the input to the DC Negative or disable the input. For further details of module configuration, refer to DSE Publication: 057- 201 DSE46xx Configuration Software Manual. To check the start cycle operation, take appropriate measures to prevent the engine from starting •...
  • Page 81: Fault Finding

    Commissioning - Fault Finding 9 FAULT FINDING 9.1 STARTING Symptom Possible Remedy Unit is inoperative Check the battery and wiring to the unit. Check the DC supply. Check the DC fuse. Read/Write configuration does not operate Unit shuts down Check DC supply voltage is not above 35 Volts or below 9 Volts Check the operating temperature is not above 70°C.
  • Page 82: Alarms

    Commissioning - Fault Finding 9.3 ALARMS Symptom Possible Remedy Low oil Pressure fault Check engine oil pressure. Check oil pressure switch/sensor and operates after engine has wiring. Check configured polarity (if applicable) is correct (i.e. fired Normally Open or Normally Closed) or that sensor is compatible with the module and is correctly configured.
  • Page 83: Miscellaneous

    Commissioning - Fault Finding 9.5 MISCELLANEOUS Symptom Possible Remedy Module appears to ‘revert’ to When editing a configuration using the PC software it is vital that the an earlier configuration configuration is first ‘read’ from the controller before editing it. This edited configuration must then be “written”...
  • Page 84: Maintenance, Spares, Repair And Servicing

    In the case of malfunction, you should contact your original equipment manufacturer (OEM). 10.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE If you require additional plugs from DSE, please contact our Sales department using the part numbers below. 10.1.1 PACK OF PLUGS...
  • Page 85: Warranty

    Warranty 11 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, you are referred to your original equipment supplier (OEM). DISPOSAL 12.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
  • Page 86 This Page is Intentionally Left Blank...