V2 TORQ-A Manual page 42

230v electro-mechanical irreversible rack actuator for sliding gates up to 800 kg
Table of Contents

Advertisement

Available languages

Available languages

12.2 - ACTIVATING/DEACTIVATING START
AND PEDESTRIAN LOCK
Default = wired start and start button on PCB activated.
This programming sequence allows for locking the "start" / "ped"
wired input and the start button on the control unit. This may be
useful for controlling the automation exclusively via radio.
1.
Press the SET, RADIO and START buttons simultaneously for 3
seconds, all the LEDs go out
2.
Press the SET button for 1 second:
-
If the red "error" LED is on lock = activated
(if it is the correct setting go to point 5 if not proceed with
point 3)
-
If the red "error" LED is off block = deactivated
(if it is the correct setting go to point 5 otherwise go to
point 4)
3.
Press the START button for 1 second, the yellow "set" LED
remains lit and the red "error" LED goes out. Go to step 5
4.
Press the START button for 1 second, the yellow "set" LED
remains on and the red "error" LED lights up
5.
Press the SET and RADIO buttons simultaneously or wait 10
seconds to exit the procedure: the LEDs return to the normal
operating configuration
m
If the command lock is activated, any device connected
to the "start" and "ped" contacts will not be detected by
the control unit. When these contacts are closed, the green
"start" LED will emit brief flashes.
13. OTHER FUNCTIONS
m
To interrupt the following programming sequences at
any time, press the SET and RADIO buttons simultaneously
or wait 10 seconds.
13.1 - ACTIVATING/DEACTIVATING THE
CONTROL UNIT PROTECTION DEVICE
Default = control unit protection device not active.
m
This programming sequence allows for locking all
control unit programming sequences and the settings
adjustable through the dip-switches. To perform a new
programming sequence or make a dip-switch/trimmer
modification effective, the protection must be deactivated.
1.
Press the SET, RADIO and START buttons simultaneously for 3
seconds, all the LEDs go out
2. -
If the yellow "set", red "radio" and green "start" LEDs
remain lit: central block = activated (if it is the correct
setting go to point 5 if not proceed with point 3)
-
If the yellow "set", red "radio" and green "start" LEDs are
off: central block = deactivated (if it is the correct setting,
go to point 5 if not, proceed to point 3)
3.
Press the START and RADIO buttons simultaneously for 2
seconds: the yellow "set", red "radio" and green "start"
LEDs go out. Go to step 5
4.
Press the START and RADIO buttons simultaneously for 2
seconds the yellow "set", red "radio" and green "start" LEDs
light up
5.
Press the SET and RADIO buttons simultaneously or wait 10
seconds to exit the procedure: the LEDs return to the normal
operating configuration
13.2 - RESETTING THE CONTROL UNIT'S
DEFAULT PARAMETERS
m
This procedure allows for restoring the control unit's
parameters to their default values.
The procedure leaves the memorised radio transmitters
unaltered. To reset the radio memory as well, see Paragraph
7.3.
1.
Press the START button for 8 seconds or until all leds are
flashing: all led flash
2.
Release START button
3.
Press START button for 3 seconds: all led light up in series
4.
Reset is now completed: the ERROR led flashes 3 times
continuosly
5.
A new programming of the gate travel is required
- 40 -