Specification - Siemens FDOOT271-O Technical Manual

Radio fire detector
Hide thumbs Also See for FDOOT271-O:
Table of Contents

Advertisement

Planning
4
Parameter sets for FDOOT271-O

4.2.1.3 Specification

No.
Name
0
Robust
2
Robust
5
Suppression
6
Fast Response
28 | 50
The following table displays the properties and fields of application of the
parameter sets of radio fire detector FDOOT271-O in sensor mode 0.
Optical
Typ. Response
Sensitivity,
time
open fire
from - typ. - to
[s]
[%/m]
80
3.2
80
3.2
90 -160 - 760
3.2
20 - 30
1.6
1
Applicable with fast temperature increases >10 K/min.
The following table shows which product version ES meets which standard for the
parameter sets.
No.
Name
0
Robust
2
Robust
5
Suppression
6
Fast Response
Sensitivity,
Static
smoldering fire
activation
temperature
[%/m]
[°C]
11.4
80
11.4
80
11.4
80
5.6
80
Thermal
Differential activation
Differential
1
temperature 
activation
possible from:
∆T [K]
29
29
29
25
ES <8
ES ≥8
EN 54-7
EN 54-7, EN 54‑29
EN 54-7
EN 54-7, EN 54‑29
EN 54-7
EN 54-7, EN 54‑29
EN 54-7
EN 54-7, EN 54‑29
A6V10425624_en--_h
[°C]
30
30
30
3