Parameter Sets For Fdoot271-O; Sensor Mode 0 'Neural Fire Detector; Description; Use - Siemens FDOOT271-O Technical Manual

Radio fire detector
Hide thumbs Also See for FDOOT271-O:
Table of Contents

Advertisement

4.2 Parameter sets for FDOOT271-O

4.2.1 Sensor mode 0 'Neural fire detector'

4.2.1.1 Description

4.2.1.2 Use

No. Name
Risk of damage to
persons
small...
large
0
Robust
2
Robust
5
Suppression
6
Fast Response
A6V10425624_en--_h
(Parameter set numbers in brackets)
Robust (0)/(2):
The priority of the 'Robust' parameter set is to a robust response. It is thus
particularly suited to application in rooms where deceptive phenomena such as
cigarette smoke or dust can be expected. The 'Robust (2)' parameter set is suitable
for higher rooms.
Suppression (5):
Thanks to its very robust behavior, the 'Suppression' parameter set is particularly
suitable for rooms where deceptive phenomena such as cigarette smoke or
exhaust fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
Concentration of
valuable items
low...
high
Parameter sets for FDOOT271-O
Room
Deceptive
geometry
phenomena
simple...
few...
complex
many
Planning
Risk of fire
Critical fire size
small...
small...
large
medium
27 | 50
4

Advertisement

Table of Contents
loading

Table of Contents