Figure 4-19 Removal of the internal EMC filter (size 2 shown)
1
To electrically disconnect the internal EMC filter, remove the screw as shown above (1).
4.5.3
Further EMC precautions
Further EMC precautions are required if more stringent EMC emission requirements apply:
•
Operation in the first environment of EN 61800-3: 2004
•
Conformity to the generic emission standards
•
Equipment which is sensitive to electrical interference operating nearby
In this case it is necessary to use:
•
The optional external EMC filter
•
A shielded motor cable, with shield clamped to the grounded metal panel
•
A shielded control cable, with shield clamped to the grounded metal panel
Full instructions are given in the Drive User Guide.
A full range of external EMC filters are also available for use with Unidrive M200 / 201.
24
Unidrive M200-201 Quick Start Guide
Issue Number: 5