PUTTING IT INTO SERVICE
• setpoint
• the external temperature measured by sensor T4
• input status
the electronic board makes all the necessary temperature
adjustments to satisfy the heating/cooling or not water pro-
duction needs by operating on the relays and (by means of
PLL logic) on the external condenser signal.
Hot water production, which has higher priority over the
other adjustments, sets heat pump operation of the exter-nal
unit until the desired setpoint is reached (default setting
45°C, adjustable between 30 and 50°C) and simultaneously
activates the three-way valve in order to divert the hot water
produced in the boiler.
This adjustment is indicated by the switching on of the ap-
propriate LED
This function can be disabled by the Technical Service Centre
and in this case the system sensor (T1) will appear automat-
ically on the display, and the hot water sensor (T3) will be
ignored.
The cooling function
is enabled:
• by the closing of the ON/OFF
• of the thermostatic contact TA
to select press the button
The key
sets the production of cold water to exploit the
inverter adjustment modulation to the maximum by means
of a PLL logic which acts according to the actual different be-
tween the temperature measured by the probe on the sys-
Access to user menu, displaying and modifying information
press the key
press the button
INFO MENU
press the
key to view the value
press the
tive function SET or the active function SAN
press the
or
Release the key
The 'next parameter' will be displayed.
User menu
press the
the menu
The information available is:
• T1
Plant probe temperature
• SET
Active function setpoint (cooling or heating)
• T2
Heat exchanger output sensor temperature*
• SAN
Hot water function setpoint
• T3
Hot water sensor temperature (default view)
Stand-by
Standby state can be set using the touch screen interface or
by opening the ON/OFF selection contact connected to ter-
minals 7 – 8.
The display shows OFF, deactivating all settings.
While in stand-by, the device runs an antifreeze cycle
which activates the circulation pump based on the ALO
threshold and on the readings of sensors T2 and T3.
Operation is signalled on the display by the alternating
OFF and ALO signs.
42
and then immediately release
or
to view the data in the
key to change the setpoint of the ac-
to set the desired value
and the new value is stored.
to access the information available in
tem water return and the setpoint SET set to 12 °C (adjustable
between 10 and 20 °C).
This adjustment is indicated by the switching on of the
LED
.
The heating function
is enabled:
• by the specific switch on the control panel
• by the closing of the ON/OFF
• of the thermostatic contact TA
to select press the button
The key
imposes a PLL logic that operates by taking into
account both the actual difference between the temperature
detected by the probe on the return of the water from the
system and the SET setpoint set at 40 °C (adjustable between
20 and 55 °C) and the outside air temperature (climatic reg-
ulation), so as to make the outdoor unit work in heat pump
mode, exploiting the modulation algorithm to the maximum
and, if necessary, activate the auxiliary heater according to
the envisaged regulations.
This adjustment is indicated by the switching on of the
LED
The external condenser is enabled whenever a thermostatic
request is received in accordance with the integration and
switching settings.
The external condenser is disabled in case of alarm.
Disabling is indicated by the LED lighting
Settings are mutually excluding and the setting remains
stored also in case of blackout.
press the
button to exit the menu or wait 10 sec-
onds
• T4
External air sensor temperature
• Mhr Thousand of hours of resistor operation
• Phr
Resistance hours of operation
• MhC
Thousand of hours of resistor operation
• PhC
Heat pump operation hours
• Loc
Keypad state (locked)**
* Subject to climatic control
** Select YES to lock keypad or NO to unlock it