Enable/Disablements - EMS SmartCell User Manual

Wireless control panel
Hide thumbs Also See for SmartCell:
Table of Contents

Advertisement

Total devices
The 'Total Devices' option indicates the total number of devices on the system. Upon entry, the individual
device details along with its current status are shown. The device list starts at the lowest device address
number and can be scrolled through, using the

Enable/disablements

The 'Enable/Disablements' menu allows the user to enable or disable individual devices or zones on the
system. The user has the ability to make permanent or timed disablements. Timed disablements can be
made for durations between 1 to 24 hours, in 1 hour increments. The front display will change to indicate
active disablements, as detailed below.
Fire Control Panel
Disablements Active
12:12
Fire zone
The 'Fire Zone' option allows the user to select individual zones ranging between the fire zones programmed
on the system (max 1-48). The zones can be disabled or enabled from this menu. The zones can also be
disabled for a time period from this menu programmable between 1-24 hours in 1 hour steps. No fault or fire
conditions will be displayed from any device that is associated to a disabled zone.
Fire devices
The 'Fire Devices' option allows the user to select individual devices. The device can be disabled or enabled
from this menu. The devices can also be disabled for a time period from this menu programmable between
1-24 hours in 1 hour steps. No fault or fire conditions will be displayed from any device that is currently
disabled.
Please note; if disabled is selected and a dual device input device is being used I.e. dual heat/smoke
detection or a dual input/output device, both elements will be disabled. It is possible to select individual
elements of the device to be disabled. This is achieved by selecting the 'Individual' menu option. Upon
selection, it is possible to select the individual elements that you wish to disable. See the example display
below, detailing the available options for a dual detector with combined sounder:
©2021 EMS Ltd. All rights reserved.
and
1
3
View>
Heat
Smoke
Sound
Option
Page 20 of 28
buttons.
Fire Control Panel
Disablements Active
10/01/20
ENABLED
ENABLED
ENABLED
Change>
TSD113-0001-99 (Issue 3) 19/05/2021 AJM