Chapter 11. 3DM 2 Reference
214
. Indicates the BBU serial number.
Serial Number
Indicates if the BBU is able to backup the 3ware RAID
BBU Ready.
controller or not. If the BBU is "Ready", write cache can be enabled on the
3ware RAID controller. When the status is not "Ready," write caching is
automatically disabled on all units attached to the controller.
Indicates the status of the BBU. Possibly BBU statuses include
BBU Status.
the following:
. The BBU is functioning normally.
OK
. The BBU was not detected or is disabled. (The BBU can be
Not Present
disabled using CLI.)
. No battery pack is installed in the BBU.
No Battery
. A battery capacity test is in process.
Testing
. The battery is being charged. Charging of the battery occurs
Charging
automatically if the battery voltage falls too low. This normally occurs
about once a week to top off the charge level; the process does not change
the BBU readiness state.
If the battery is ever discharged through a backup cycle or if the system
power is off for more than two weeks, the battery status changes to
"Charging" the next time the system is powered on. This indicates the
BBU is not able to backup the 3ware RAID controller. When the BBU is
in the charging state, write caching is disabled automatically on all units
attached to the controller.
Fault
. The BBU detected a fault. This occurs if the voltage or temperature
is outside the acceptable range.
. Other BBU error. Please contact AMCC Technical Support.
Error
Weak Battery
. The battery should be replaced soon. The results of a
battery health test or capacity test indicate that the battery is below the
warning threshold (48 hours).
. The battery failed a test and must be replaced. A "Failed
Failed Battery
Battery" status is displayed if the battery failed the health test or the
battery capacity is below the error threshold (24 hours). The battery must
be replaced.
Battery Voltage.
Indicates the voltage status of the battery. The BBU
measures and evaluates the battery voltage continuously. If the voltage falls
outside the normal range, warning or error level AENs are generated. In the
case of a voltage error the BBU status will change to "Fault" and the battery
will be disconnected electronically.
. Indicates the temperature status of the battery. The
Battery Temperature
BBU measures and evaluates the battery pack temperature continuously. If the
temperature falls outside the normal range, warning or error level AENs are
3ware Serial ATA RAID Controller User Guide