10.2.4 Frequency signal for flow (OUT1)
► Select [OU1] and set FRQ�
► Select [FEP] and set the flow value at which the frequency set in FrEP
is provided�
► Select [FrEP] and set the frequency�
10.3 Settings for consumed quantity monitoring
10.3.1 Quantity monitoring by pulse output (OUT1)
► Select [OU1] and set ImP�
► Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 10.3.3)�
► Select [ImPR] and set [YES]�
> Pulse repetition is active� Output 1 provides a counting pulse each time
the value set in [ImPS] is reached�
10.3.2 Quantity monitoring by preset counter (OUT1)
► Select [OU1] and set ImP�
► Select [ImPS] and set the volumetric flow quantity at which output 1
switches (→ 10.3.3)�
► Select [ImPR] and set no�
> Pulse repetition is not active� The output switches ON if the value set in
[ImPS] is reached� It remains switched until the counter is reset�
10.3.3 Pulse value
► Select [OU1] and set the consumed quantity to be monitored:
→ 10.3.1 or → 10.3.2�
► Select [ImPS]�
► Briefly press [Enter]�
> The currently set value is displayed�
► keep [▲] or [▼] pressed until "cccc
► Press [▲] or [▼]
> With each press of the pushbutton the display changes to the next
setting range (decimal point shifts and / or LED* changes)�
► Press [Enter] to confirm the setting range�
► Press [▲] or [▼] until the requested numerical value is displayed.
► Briefly press [Enter]�
* → 7 Operating and display elements
Main menu:
[OU1]
[FEP]
[FrEP]
Main menu:
UK
[OU1]
[ImPS]
[ImPR]
Main menu:
[OU1]
[ImPS]
[ImPR]
Main menu:
[OU1]
[ImPS]
35