10 Installation Information

10.1. ATTACHED ACCESSORIES

10.2. SELECT THE BEST LOCATION

10.2.1. INDOOR UNIT
· There should not be any heat source or steam near the unit.
· There should not be any obstacles blocking the air circulation.
· A place where air circulation in the room is good.
· A place where drainage can be easily done.
· A place where noise prevention is taken into consideration.
· Do not install the unit near the door way.
· Ensure the spaces indicated by arrows from the wall, ceiling or other obstacles.
· Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3m.
10.2.2. OUTDOOR UNIT
· If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not
obstructed.
· There should not be any animal or plant which could be affected by hot discharged air.
· Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
· Do not place any obstacles which may cause a short circuit of the discharged air.
10.2.3. PIPING LENGTH
MODEL
VC70KE
VC90KE
VC120KE
*1.The additional gas charge is unnecessary up to the Max. piping length. (CS-VC70KE, CS-VC90KE)
*2. The above models (CS-VC120KE) will be installed at a 15 m (max) distance.
The refrigerant should be added 75g. ( 15m - 10m ) x 15g = 75g
Piping size
Rated
Length (m)
Gas
Liquid
3/8"
1/4"
3/8"
1/4"
1/2"
1/4"
35
CS-VC70KE / CU-VC70KE / CS-VC90KE / CU-VC90KE / CS-VC120KE / CU-VC120KE
Max. Elevation
(m)
7
5
7
5
10
5
Max. Piping
Length (m)
10
10
15