Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
PNOZ X8P Introduction Validity of documentation This documentation is valid for the product PNOZ X8P. It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
This gives advice on applications and provides information on special fea- tures. Safety Intended use The safety relay PNOZ X8P provides a safety-related interruption of a safety circuit. The safety relay meets the requirements of EN 60947-5-1 and EN 60204-1 and may be used in applications with: E-STOP pushbuttons...
Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V. Operating Manual PNOZ X8P 19820-EN-10...
The circuit is redundant with built-in self-monitoring. The safety function remains effective in the case of a component failure. The correct opening and closing of the safety function relays is tested automatically in each on-off cycle. Operating Manual PNOZ X8P 19820-EN-10...
: 24 VAC; Order no. 787770 : 110 VAC; Order no. 777764, 787764 : 230 VAC; Order no. 777768, 787768 *Insulation between the non-marked area and the relay contacts: Basic insulation (over- voltage category III), Protective separation (overvoltage category II) Operating Manual PNOZ X8P 19820-EN-10...
PNOZ X8P Function Description The safety relay PNOZ X8P provides a safety-oriented interruption of a safety circuit. When supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the feedback loop Y1-Y2 and the start circuit S33-S34 are closed. The "START" LED is lit.
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm). When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket or end angle). Operating Manual PNOZ X8P | 11 19820-EN-10...
Important for detection of shorts across contacts: As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during the final control check. If there is a danger of exceeding the cable runs, we recommend the following test after the installation of the device: 1.
ESPE (only when U = 24 VDC) NOTICE With single-channel wiring the safety level of your machine/plant may be lower than the safety level of the unit (see Safety characteristic data). Operating Manual PNOZ X8P | 13 19820-EN-10...
Page 14
PNOZ X8P NOTICE Operation with a light guard or safety switch It must not be possible to switch off the supply voltage for the PNOZ X8P separately from the supply voltage for the light guard or safety switch. Start circuit...
SIL CL 2/PL d at least 1x per year NOTICE The safety function should be checked after initial commissioning and each time the plant/machine is changed. The safety functions may only be checked by qualified personnel. Operating Manual PNOZ X8P | 15 19820-EN-10...
Start circuit is closed. CH.1 IN Channel 1 input circuit is closed. CH.2 IN Channel 2 input circuit is closed. CH.1 Safety contacts of channel 1 are closed. CH.2 Safety contacts of channel 2 are closed. Operating Manual PNOZ X8P | 16 19820-EN-10...
Contact malfunctions: If the contacts have welded, reactivation will not be possible after the input circuit has opened. LED "POWER" does not light: Short circuit or no supply voltage. Dimensions in mm * With spring-loaded terminals Operating Manual PNOZ X8P | 17 19820-EN-10...
40 mA 40 mA Start circuit DC 50 mA 60 mA 60 mA Feedback loop DC 50 mA 60 mA 60 mA Min. input resistance at power-on 89 Ohm 89 Ohm 89 Ohm Operating Manual PNOZ X8P | 18 19820-EN-10...
Page 19
Number of output con- tacts Safety contacts (N/O), instantaneous Auxiliary contacts (N/C) 2 Max. short circuit current 1 kA 1 kA 1 kA Utilisation category In accordance with the standard EN 60947-4-1 EN 60947-4-1 EN 60947-4-1 Operating Manual PNOZ X8P | 19 19820-EN-10...
Page 20
240 V AC G. P. 240 V AC G. P. With current Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive With current Pilot Duty B300, R300 B300, R300 B300, R300 Operating Manual PNOZ X8P | 20 19820-EN-10...
Page 21
3 contacts – Ith per contact at UB DC; AC1: 240 V, DC1: 24 V Conv. therm. current with 1 contact – – Conv. therm. current with 2 contacts – – Conv. therm. current with 3 contacts – – Operating Manual PNOZ X8P | 21 19820-EN-10...
Page 22
61000-6-2, EN 61326-3-1 Vibration In accordance with the standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6 Frequency 10 - 55 Hz 10 - 55 Hz 10 - 55 Hz Amplitude 0,35 mm 0,35 mm 0,35 mm Operating Manual PNOZ X8P | 22 19820-EN-10...
Page 23
94 mm Width 45 mm 45 mm 45 mm Depth 121 mm 121 mm 121 mm Weight 315 g 415 g 415 g Where standards are undated, the 2020-07 latest editions shall apply. Operating Manual PNOZ X8P | 23 19820-EN-10...
200 Ohm Dual-channel with detection of shorts across contacts at UB DC 16 Ohm – Dual-channel with detection of shorts across contacts at UB AC – 28 Ohm Semiconductor outputs 787760 787764 Number Operating Manual PNOZ X8P | 24 19820-EN-10...
Page 25
2000 VA DC1 at 24 V 24 V Min. current 0,01 A 0,01 A Max. current Max. power 200 W 200 W Utilisation category In accordance with the standard EN 60947-5-1 EN 60947-5-1 Operating Manual PNOZ X8P | 25 19820-EN-10...
Page 26
Ith per contact at UB AC; AC1: 240 V, DC1: 24 V Conv. therm. current with 1 con- tact – Conv. therm. current with 2 con- tacts – 7,3 A Conv. therm. current with 3 con- tacts – Operating Manual PNOZ X8P | 26 19820-EN-10...
Page 27
93 % r. h. at 40 °C 93 % r. h. at 40 °C Condensation during operation Not permitted Not permitted EN 60947-5-1, EN 61000-6-2, EN EN 60947-5-1, EN 61000-6-2, EN 61326-3-1 61326-3-1 Operating Manual PNOZ X8P | 27 19820-EN-10...
Where standards are undated, the 2020-07 latest editions shall apply. Technical details Order no. 787768-787770 General 787768 787770 CCC, CE, EAC (Eurasian), TÜV, CCC, CE, EAC (Eurasian), TÜV, Certifications cULus Listed cULus Listed Operating Manual PNOZ X8P | 28 19820-EN-10...
Page 29
Utilisation category in accordance with EN 60947-1 DC-12 DC-12 Relay outputs 787768 787770 Number of output contacts Safety contacts (N/O), instant- aneous Auxiliary contacts (N/C) Max. short circuit current IK 1 kA 1 kA Operating Manual PNOZ X8P | 29 19820-EN-10...
Page 30
Utilisation category in accordance with UL Voltage 240 V AC G. P. 240 V AC G. P. With current Voltage 24 V DC Resistive 24 V DC Resistive With current Pilot Duty B300, R300 B300, R300 Operating Manual PNOZ X8P | 30 19820-EN-10...
Page 31
180 ms Delay-on de-energisation With E-STOP typ. 15 ms 15 ms With E-STOP max. 30 ms 30 ms With power failure typ. 160 ms 160 ms With power failure max. 220 ms 220 ms Operating Manual PNOZ X8P | 31 19820-EN-10...
Page 33
8 mm Dimensions Height 101 mm 101 mm Width 45 mm 45 mm Depth 121 mm 121 mm Weight 415 g 415 g Where standards are undated, the 2020-07 latest editions shall apply. Operating Manual PNOZ X8P | 33 19820-EN-10...
If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switch frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components. Operating Manual PNOZ X8P | 34 19820-EN-10...
To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With DC con- tactors, use flywheel diodes for spark suppression. Operating Manual PNOZ X8P | 35 19820-EN-10...
European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/support/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost- fildern, Germany Operating Manual PNOZ X8P...
Page 37
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters. Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com...