Pilz PNOZ X8P Operating Manual page 30

Safety relays
Table of Contents

Advertisement

PNOZ X8P
Relay outputs
Utilisation category
In accordance with the standard EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. power
Utilisation category of auxiliary con-
tacts
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. power
Utilisation category
In accordance with the standard EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at
Max. current
DC13 (6 cycles/min) at
Max. current
Utilisation category of auxiliary con-
tacts
AC15 at
Max. current
DC13 (6 cycles/min) at
Max. current
Utilisation category in accordance
with UL
Voltage
With current
Voltage
With current
Pilot Duty
Operating Manual PNOZ X8P
19820-EN-10
787768
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
230 V
5 A
24 V
7 A
230 V
5 A
24 V
7 A
240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300
787770
EN 60947-4-1
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
EN 60947-5-1
230 V
5 A
24 V
7 A
230 V
5 A
24 V
7 A
240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300
| 30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents