PNOZ X8P

Supplementary data

Service life graph

The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.
Example
}
Inductive load: 0.2 A
}
Utilisation category: AC15
}
Contact service life: 4 000 000 cycles
Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.
Operating Manual PNOZ X8P
19820-EN-10