PNOZ X8P
Semiconductor outputs
Voltage
Current
External supply voltage
Voltage tolerance
Residual current at "0" signal
Max. internal voltage drop
Conditional rated short circuit cur-
rent
Lowest operating current
Utilisation category in accordance
with EN 60947-1
Relay outputs
Number of output contacts
Safety contacts (N/O), instant-
aneous
Auxiliary contacts (N/C)
Max. short circuit current IK
Utilisation category
In accordance with the standard EN 60947-4-1
Utilisation category of safety con-
tacts
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. power
Utilisation category of auxiliary con-
tacts
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. power
Utilisation category
In accordance with the standard EN 60947-5-1
Operating Manual PNOZ X8P
19820-EN-10
787760
24 V
50 mA
24 V
-20 %/+20 %
0,1 mA
4 V
100 A
0 mA
DC-12
787760
3
2
1 kA
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
787764
24 V
50 mA
24 V
-20 %/+20 %
0,1 mA
4 V
100 A
0 mA
DC-12
787764
3
2
1 kA
EN 60947-4-1
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
EN 60947-5-1