PNOZ X8P
Start circuit
Automatic start
Automatic start with start-up test
Manual start
Monitored start
Operating Manual PNOZ X8P
19820-EN-10
NOTICE
Operation with a light guard or safety switch
It must not be possible to switch off the supply voltage for the PNOZ X8P
separately from the supply voltage for the light guard or safety switch.
E-STOP/safety gate wiring
(single-channel, dual-channel
without detection of shorts
across contacts)
S33
S34
S33
S34
Y1
S37
NOTICE
In the event of an automatic start or manual start with bridged start
contact (fault):
The unit starts up automatically when the safeguard is reset, e.g. when the
E-STOP pushbutton is released. Use external circuit measures to prevent
an unexpected restart.
E-STOP/safety gate wiring
(dual-channel with detection of
shorts across contacts)
S3
S3
S12
S34
Y1
S37
S3