Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual page 166

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

The following system configuration can be created. Connect the necessary parts.
1. When connecting with remote controller (PZ-41SLB-E).
2. When interlocking with air conditioner or other external device.
3. When interlocking with a pulse output unit.
4. When operating multiple Lossnay units.
5. When connecting to CO
6. When connecting to City Multi, Lossnay remote controller (PZ-52SF-E) or Mitsubishi Electric Air-Conditioner Network
System (MELANS).
Lossnay
Power supply
LGH-50 and 100RX types
1
2
Remote controller input terminal
Transmission cable
Lossnay
Power supply
Lossnay
External controller input (TM2)
Within 500 m
sensor when switching the High/Low switch externally.
2
Up to two remote controllers
(PZ-41SLB-E) can be used.
LGH-200RX type
3
4
5
6
5
6
A
B
S
Remote con-
troller
(PZ-41SLB-E)
Power supply
External
device
Operating switch
for external device
Slim-Lossnay connection cable
(Enclosed accessory)
White
CN2L
Mr. Slim (A-controll)
unit
Red
Printed circuit board
1. When connecting to remote controller
(PZ-41SLB-E)
*
The PZ-41SLB-E cannot be used when centralised control
of the Lossnay is used. Then follow the procedure for con-
necting the wire shown in 6. and use the Lossnay remote
controller (PZ-52SF-E).
Securely connect the transmission cable (PVC insulated PVC
jacketed and either between ø0.65 and ø1.2, or between 0.3
2
2
mm
and 1.25 mm
in cross section) from the remote controller
to 5 and 6 of the input terminal block (TM2). (No polarity)
If there are two remote controllers, connect them in the
same way.
Note:
2
Up to four 0.3 mm
stranded wires or ø0.65 PVC wires can
be connected to one input terminal.
For other types of wire up to two can be connected.
2. When interlocked with air conditioner or
other external device
(1) Connect the output signal cable from the external device to
the input terminal block (TM2) of the external controller.
LGH-200RX type are conected to the lower circuit board.
(Main circuit board)
CAUTION:
The connection may vary according to the output signal type
of the external device.
When using Mr. Slim air conditioner and (A-control) Interlock
operation of except Mr. Slim (A-control) unit is not possible.
Connect the interlocking cable connector side to CN2L on the
circuit board for the indoor Mr. Slim unit and connect the lead
wire side to the 1 and 2 of the input terminal block (TM2) for
the Lossnay external controller input. (No polarity)
Always separate the power supply cable and the Slim-
Lossnay connection cable for the Lossnay by 5 cm or more
to prevent malfunctioning of the unit.
The Slim-Lossnay connection cable is 0.25 m long.
When wiring, extend it as far as necessary.
Note:
The Lossnay remote controller (PZ-41SLB-E) cannot be
used with this system.
The ventilation mode is "automatic ventilation".
The Slim-Lossnay connection cable may be extended to a
maximum length of 500 m (Extension cable specifications
are as detailed below).
Ensure that all connections are secure and that the appro-
priate insulation is provided.
Extension cable sheathed PVC cable or cable-0.5 mm
2
2
to 1.0 mm
.
163