Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual page 100

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

2. U.S.
ASHRAE standard 62 - 1999
Application
Dry Cleaner
Dining room
Bars
Kitchens
Hotel bedroom
Hotel living room
Hotel lobby
Casino
Office space
Conference room
Smoking lounge
Bowling alley (seating area)
3. U.K.
CIBSE
Application
Factories
Offices (open plan)
Shops, department stores and supermarkets
Theatres
Dance halls
Hotel bedrooms
Laboratories
Offices (private)
Residences (average)
Restaurant (cafeteria)
Cocktail bars
Conference rooms (average)
Residence
Restaurant
Board rooms executive offices and
conference rooms
Corridors
Kitchens (domestic)
Kitchens (restaurant)
Toilets
CHAPTER 10
Ventilation Standards in Each Country
Outdoor air recommendation
30 cfm/person
20 cfm/person
30 cfm/person
15 cfm/person
30 cfm/room
30 cfm/room
15 cfm/person
30 cfm/person
20 cfm/person
20 cfm/person
60 cfm/person
25 cfm/person
Recommended
Per person
8 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
18 l/s /person
18 l/s /person
18 l/s /person
18 l/s /person
25 l/s /person
N/A
N/A
N/A
N/A
Outdoor air
Minimum
Per person
5 l/s /person
5 l/s /person
5 l/s /person
5 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
8 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
12 l/s /person
18 l/s /person
N/A
N/A
N/A
N/A
Occupancy
2
30 people/100 m
2
70 people/100 m
2
100 people/100 m
2
20 people/100 m
2
30 people/100 m
2
120 people/100 m
2
7 people/100 m
2
50 people/100 m
2
70 people/100 m
2
70 people/100 m
Smoking
2
Per m
2
0.8 l/s / m
None
2
1.3 l/s / m
Some
2
3.0 l/s / m
Some
Some
Some
2
1.7 l/s / m
Heavy
Some
2
1.3 l/s / m
Heavy
Heavy
Heavy
Heavy
Some
Heavy
Heavy
Very
2
6.0 l/s / m
Heavy
2
1.3 l/s / m
N/A
2
10.0 l/s / m
N/A
2
20.0 l/s / m
N/A
2
10.0 l/s / m
N/A
97