4. System Features and Examples

4.1
Features
Classification
Control
• Multiple unit operation
• Remote controller operation
• External device operation
• External pulse control
• External monitor signal output
• Supply air fan monitor output
• External control operation mode setting
• Delayed start
• Automatic recovery following power sup-
• Power supply start/stop function
• High/low change input
• Remote/Local control change
• The M-NET air conditioning operation.
• Centralised control by Mitsubishi building
• Interlocked with Mr. Slim
Function
• Lossnay (heat recovery) ventilation/By-
• For cold area operation
Installation
• Remote controller 2 wires wiring
• Address setting unnecessary
• Test operation switch
Maintenance
• Filter maintenance display
• Inspection display
• M-NET power supply display
*1 The operation condition is stored, and when the power is turned off and then back on, the operation condition returns to the
previous condition. (When using PZ-41SLB-E, the start/stop condition from an external device is not stored.)
Item
ply interruption (*1)
air control management system
pass ventilation automatic switch
(non-polar)
(remote controller display)
(remote controller, control board LED)
(control board LED)
Notes/Cautions
Maximum 15 units with PZ-41SLB-E; 16 units with PZ-
52SF-E or other M-NET controller.
Last touch priority
Signal form: 12VDC, 24VDC, uncharged a-contact
Ditto
Uncharged a-contact (external monitor/supply air fan
monitor change)
Ditto
ON/OFF , ON, OFF and External priority ON/OFF mode.
Delayed time can be varied only when the PZ-41SLB-E is
connected.
Return power automatic return is fixed when the PZ-
41SLB-E is connected.
Impossible when the PZ-41SLB-E is connected.
Uncharged a-contact (Part sold separately is necessary)
Uncharged a-contact (Part sold separately is necessary)
(Connection is impossible when using PZ-41SLB-E)
Only when M-NET transmission cable is connected
Ditto
Can not use the PZ-41SLB-E
When the PZ-41SLB-E is connected: PVC cable ø 0.65
to 1.2 or strand wire 0.3 mm
When M-NET is connected: shielded wire or equivalent
2
2
1.25 mm
to 2.00 m
.
Excluding central controller system (except automatic
address)
For Lossnay single unit test operation
2
2
to 1.25 mm
.
109