Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual page 132

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

5.2
Delayed Interlocked Operation
(PZ-41SLB-E, M-NET)
(1) It is possible to delay operation of the Lossnay with respect to the operation of the external device. (Energy saving effect.)
(2) The times that can be set for delayed operation are 10, 20, 30, 40, 50, and 60 minutes.
(3) Delayed operation does not occur if the Lossnay operation was cancelled within the last 2 hours.
(If turned off for a short time, for example during a lunch break, if the direction to restart operation is given within 2 hours, the
Lossnay will restart immediately.)
(4) If an operation button is pressed on the remote controller while the delay timer is operating, the delayed operation is can-
celled and normal operation begins.
Setting Method
When PZ-41SLB-E is used . . . . . . Set with the remote controller. (Refer to page 174)
When PZ-41SLB-E is Not used . . . Set with the dip switch but fixed only for 30 minutes. (Refer to page 167)
5.3
Multiple External device Operation
(PZ-41SLB-E, M-NET)
When there are multiple air conditioners or other external devices
Characteristics
Lossnay operates when any of the
external devices operate.
System Example
When the Operation Signal is a Uncharged a-contact Level Signal
(Signal cable for space
between Lossnay and
remote controller is less
than 500 m.)
PVC cable φ 0.65 to 1.2
or strand wire 0.3 mm
2
to 1.25 mm
.
Remote controller
Lossnay
Power supply
2
Remote controller
PZ-41SLB-E
Ordered parts
Uncharged a-contact
Air condi-
tioner 1
Power supply
Air conditioner
remote controller
* Illustration shows an example when using PZ-41SLB-E.
Notes
• External signals that can be
received are listed below.
Level signal, uncharged a-contact
• If the external device is a pulse sig-
nal or charged signal multiple con-
nections can not be made.
Uncharged a-contact
Uncharged a-contact
Air condi-
Air condi-
tioner 2
tioner 4
Power supply
Air conditioner
Air conditioner
remote controller
remote controller
Power supply
129