(1) Checklist of error codes displayed on the PZ-41SLB and LED displays (Table 2-1)
LED1
LED 2
Error code
(green)
(red)
LC 6608
RC6608
SRC 6608
LC 0900
SLC 0900
LC 4000
2
blinks
SLC 4000
LC 3602
3
blinks
SLC 3602
LC 5101
4
blinks
SLC 5101
LC 5102
5
blinks
SLC 5102
———
9
blinks
"Filter" blink-
ing
"HO" blinking blink-
ing
*1 LC: Lossnay set to Main SLC: Lossnay set to Sub RC, SRC: remote controller (PZ-41SLB-E)
*2 Because the LGH-200RX type is loaded with 2 control circuit units, "SLC" may display even with only 1 Lossnay.
When "SLC" displays, check and perform maintenance on the upper side circuit.
Symptom
« When using multiple Lossnay units, the
Lossnay
communi-
main/sub setting has not been made
cation
for the second unit and following units.
error
« Multiple transmission cables have
been wired using multi core wires.
« Transmission cable and power
cable are too close.
« Transmission cable is not securely
connected.
« The length of wiring of the transmis-
sion cable is longer than specifica-
tion (longer than 500 m).
« Multiple transmission cables have
Communi-
cation error
been wired using multi core wires.
between
« Transmission cable and power sup-
remote con-
ply cable are too close.
trollers
« Transmission cable is not securely
(when 2
connected.
remote con-
« The length of wiring of the transmis-
trollers are
sion cable is longer than specifica-
connected)
tion (longer than 500 m).
« Trial operation switch on the Loss-
Lossnay
trial opera-
nay circuit board (SW 2-1 or SW 2-
tion
3) is set to ON board.
« Lossnay fan will not stop.
Fan motor
operation
device error
« Damper board operation is not cor-
Damper
related
rect.
error
« Connectors for the damper unit are
not correctly connected.
« Connectors for the thermistor are
OA thermis-
tor related
not correctly connected.
error
« Connectors for the thermistor are
RA thermis-
tor related
not correctly connected.
error
« Multiple transmission cables have
Remote
controller
been wired using multi core wires.
communi-
« Transmission cable and power sup-
cation
ply cable are too close.
error
« Transmission cable is not securely
connected.
« The length of wiring of the transmis-
sion cable is longer than specifica-
tion (longer than 500 m).
Warning to clean air
« Interval for cleaning Lossnay air fil-
filter by comulative
ter has elapsed.
operation time
System is
« LED1 blinks at 1 second intervals during
starting
starting operation (maximum of 45 seconds.)
Cause
Corrective action
« Turn off the main power supply and set the
Main/Sub switch (SW1) (first unit to main, second
and following units to sub). (refer to page 164)
« Wire the transmission cable away
from the other transmission cable.
« Wire the transmission cable at least 5
cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 163)
« Check the length of the transmis-
sion cable wiring.
« Wire the transmission cable away
from the other transmission cable.
« Wire the transmission cable at least 5
cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 174)
« Check the length of the transmis-
sion cable wiring.
« Check the test operation switch.
(refer to page 169)
« Replace the table.
« Remove the load and check or
move the damper board by hand.
« Check the connection of the lead wire's
connectors and the circuit connector.
« Check the connection of the lead
wires connectors and the circuit
connector.
« Check the connection of the lead
wires connectors and the circuit
connector.
« Wire the transmission cable away
from the other transmission cable.
« Wire the transmission cable at least 5
cm away from the power supply cable.
« Check the transmission cable con-
nection. (refer to page 163, 164)
« Check the length of the transmis-
sion cable wiring.
« After cleaning the air filter press the
"Filter" button on the remote con-
troller 2 times.
« There is no error.
151