10-1. Installation Diagram of Indoor and Outdoor Units
3
Batteries
6
Flat head
4
Remote control
wood screw
holder
2
Wireless remote control
• Loading Batteries
1. Remove the battery cover.
2. Insert 2 new batteries (AAA type)
following the (+) and (- ) positions.

10. INSTALLATION PROCEDURE

Hook
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Vinyl tape
Apply after carrying
out a drainage test.
Before installing the wireless remote controller
2 Wireless remote controller
- 57 -
1
Installation
plate
Insert the cushion between the indoor
unit and wall, and tilt the indoor unit for
better operation.
The auxiliary piping can be connected to
Bush body
the left, rear left, rear right, right, bottom
right or bottom left.
Shield pipe
Do not allow the drain hose to get slack.
Make sure to run the drain hose sloped
downward.
The fl are connection should be installed
outdoors.
Insulate the refrigerant pipes separately
with insulation, not together.
3 Batteries
FILE NO. SVM-18047
For the rear left and left piping
Wall
Right
Rear
right
Left
Bottom
Rear
right
left
Bottom left
Cut the piping
hole sloped
slightly.
6 mm thick heat resisting
polyethylene foam