10-5. Others
10-5-1. Remote Control A-B Selection
• When two indoor units are installed in the same room
or adjacent two rooms, if operating a unit, two units
may receive the remote control signal simultaneously
and operate. In this case, the operation can be
preserved by setting either one remote control to B
setting. (Both are set to A setting in factory shipment.)
• The remote control signal is not received when the
settings of indoor unit and remote control are different.
• There is no relation between A setting/B seting and
A room/B room when connecting the piping and
cables.
To separate using of remote control for each indoor
unit in case of 2 air conditioner are installed near.
Remote Control B Setup.
1) 1) Press RESET button on the indoor unit to turn
the air conditioner ON.
2) Point the remote control at the indoor unit.
3) 3) Push and hold CHK • button on the Remote
Control by the tip of the pencil. "00" will be shown
shown on the display
4) Press MODE • during pushing CHK • . "B" will
show on the display and "00" will disappear and
the air conditioner will turn OFF. The Remote
Control B is memorized (Picture 2).
Note :
1.
Repeat above step to reset Remote Control
to be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from
factory is A.
F ig. 10-5-1
(Picture
).
2
10-6-3. Test operation
To switch the TEST RUN (COOL) mode, press
Temporary switch for 10 sec.
(The unit will make a short Pi sound.)
10-6-4. Auto restart
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn ti on as required.
<How to set the auto restart>
1. Press and hold the [RESET] button on the indoor unit
3 seconds to set the operation. (3 beep sound and
OPERATION lamp blink 5 time/sec for 5 seconds)
2. Press and hold the [RESET] button on the indoor
unit for 3 seconds to cancel the operation. (3 beep
sound but OPERATION lamp does not blink)
In case of ON timer or OFF timer are set, AUTO
RESTART OPERATION does not activate.
- 68 -
FILE NO. SVM-18047
Temporary switch
F ig. 10-5-2