Toshiba MMC-AP0188HPUL Service Manual page 67

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
F24
F24
F29
F31
F31
01: Compressor 1
side
02: Compressor 2
side
H01
H01
03: Compressor 3
side
01: Compressor 1
side
02: Compressor 2
side
03: Compressor 3
side
H02
H02
01: Compressor 1
side
02: Compressor 2
H03
H03
side
03: Compressor 3
side
H05
H05
H06
H06
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Location
Description
System status
of
detection
I/F
Pd sensor
All stop
error
Indoor
Other indoor
Stop of
unit
error
corresponding
unit
I/F
Outdoor
All stop *1
EEPROM
error
IPDU
Compressor
All stop
breakdown
IPDU
Compressor
All stop
error (lockup)
MG-CTT error
IPDU
Current
All stop
detection
circuit error
I/F
TD1 sensor
All stop
miswiring
(incomplete
insertion)
I/F
Activation of
All stop
low-pressure
protection
- 67 -
Error detection
Check items (locations)
condition(s)
Output voltage of Pd
Check connection of Pd
sensor connector.
sensor is zero (sensor
open-circuited).
Check for defect in Pd sensor.
Pd > 4.15 MPa despite
Check for defect in outdoor
compressor having been
P.C. board (I/F).
turned off.
Indoor P.C. board does not
Check for defect in indoor P.C.
operate normally.
board (faulty EEPROM)
Outdoor P.C. board (I/F)
Check power supply voltage.
Check power supply noise.
does not operate normally.
Check for defect in outdoor
P.C. board (I/F).
Inverter current detection
Check power supply voltage.
circuit detects overcurrent
(380-415V ± 10 %).
and shuts system down.
Check for defect in
compressor.
Check for possible cause of
abnormal overloading.
Check for defect in outdoor
P.C. board (A3-IPDU).
Overcurrent is detected
Check for defect in
several seconds after
compressor.
startup of inverter
Check power supply voltage.
compressor.
(380-415V ± 10 %).
Check compressor system
wiring, particularly for open
phase.
Check connection of
connectors / terminals on A3-
IPDU P.C. board.
Check conductivity of case
heater.
(Check for refrigerant
entrapment inside
compressor.)
Check for defect in outdoor
P.C. board (A3-IPDU).
Check outdoor MG-CTT.
Current flow of at least
Check current detection circuit
wiring.
specified magnitude is
detected despite inverter
Check defect in outdoor P.C.
compressor having been
board (A3-IPDU).
shut turned off.
Discharge temperature of
Check installation of TD1
sensor.
compressor 1 (TD1) does
not increase despite
Check connection of TD1
compressor being in
sensor connector and wiring.
operation.
Check resistance
characteristics of TD1 sensor.
Check for defect in outdoor
P.C. board (I/F).
Low-pressure Ps sensor
Check service valves to
confirm full opening
detects operating pressure
lower than 0.02 MPa.
(both gas and liquid sides).
Check outdoor PMVs for
clogging (PMV1, 2).
Check for defect in SV2 or SV4
circuits.
Check for defect in low-
pressure Ps sensor.
Check indoor filter for clogging.
Check valve opening status of
indoor PMV.
Check refrigerant piping for
clogging.
Check operation of outdoor fan
(during heating).
Check for insufficiency in
refrigerant quantity.
MG-CTT: Magnet contactor