Toshiba MMC-AP0157HP-E Installation Manual
Hide thumbs Also See for MMC-AP0157HP-E:

Advertisement

Quick Links

AIR CONDITIONER (MULTI TYPE)
Installation Manual
Indoor Unit
Model name:
Ceiling Type
MMC-AP0157HP-E
MMC-AP0187HP-E
MMC-AP0247HP-E
MMC-AP0277HP-E
MMC-AP0367HP-E
MMC-AP0487HP-E
MMC-AP0567HP-E
For commercial use
English
.

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMC-AP0157HP-E

  • Page 1 English AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit For commercial use Model name: Ceiling Type MMC-AP0157HP-E MMC-AP0187HP-E MMC-AP0247HP-E MMC-AP0277HP-E MMC-AP0367HP-E MMC-AP0487HP-E MMC-AP0567HP-E...
  • Page 2: Table Of Contents

    – 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. 1 Precautions for safety ....................3 • This Manual describes the installation method of the indoor unit. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. 2 Accessory parts ......................
  • Page 3 Shoes with additional protective toe cap heavy objects made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has Repair of outdoor unit...
  • Page 4: Precautions For Safety

    – 3 – ■ Warning indications on the air conditioner unit Precautions for safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this Warning indication Description manual. WARNING WARNING WARNING ELECTRICAL SHOCK HAZARD General Disconnect all remote ELECTRICAL SHOCK HAZARD...
  • Page 5 Installation Explanations given to user • When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must be • Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know used.
  • Page 6: Accessory Parts

    – 5 – Accessory parts Selection of installation place Avoid installing in the following places. Part name Q’ty Shape Usage Select a location for the indoor unit where the cool or warm air will circulate evenly. (Hand over to customers) Avoid installation in the following kinds of locations.
  • Page 7: Installation

    ■ Installation space Installation (Unit: mm) Reserve suffi cient space required for installation or service work. CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) 250 or more 250 or more •...
  • Page 8: Before Installation

    – 7 – ■ ■ Installation of hanging bolt Installation of hanging bolt Before installation CAUTION Use M10 hanging bolts (4 pcs, locally procured). • Consider the piping / wiring after the unit is hung to Removal of air intake grille Matching to the existing structure, set pitch according determine the location of the indoor unit installation 1) Remove the screws of air intake grille fi...
  • Page 9: Installation Of Indoor Unit

    ■ ■ Draw-out direction of pipe / Installation of indoor unit <In case of taking pipe from upper side> ◆ Holding down of main unit Taking pipe from upper side is applied only to the wire refrigerant pipe. <Hanging the indoor unit directly from the ◆...
  • Page 10: Drain Piping

    – 9 – ◆ Attaching the hanging bracket Attach the indoor unit onto the hanging Drain piping fi rst bracket and fasten it tight with the bolts and screws. bracket Remove the screws fastening hanging CAUTION onto the indoor unit. Following the Installation Manual, perform the drain piping work so that water is properly drained.
  • Page 11 ■ ■ Connection of drain hose Heat insulating process • Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end. • Using the attached drain hose heat insulator, lap the connecting section and the drain hose without clearance, •...
  • Page 12: Refrigerant Piping

    – 11 – ■ * In case of fl aring for R410A with the conventional Evacuation Refrigerant piping ■ Connecting refrigerant piping fl are tool, pull it out approx. 0.5 mm more than that for R22 to adjust to the specifi ed fl are size. The Perform vacuuming from the charge port of valve of copper pipe gauge is useful for adjusting projection the outdoor unit by using a vacuum pump.
  • Page 13: Electrical Connection

    Heat insulation process Electrical connection Apply heat insulation for the pipes separately at liquid side and gas side. • For the heat insulation to the pipes at gas side, use CAUTION the material with heat-resisting temperature 120 °C or higher. •...
  • Page 14 – 13 – ▼Power supply ◆ Wire connection 220-240 V ~, 50 Hz REQUIREMENT Power supply 220 V ~, 60 Hz • Connect the wires matching the terminal numbers. Incorrect connection causes a trouble. Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by •...
  • Page 15: Applicable Controls

    ■ Remote controller wiring Applicable controls Strip off approx. 9 mm the wire to be connected. ■ Basic procedure for changing REQUIREMENT Wiring diagram settings When the air conditioner is used for the fi rst time, it will Terminal block for take some moments after the power has been turned remote controller Terminal block...
  • Page 16: Filter Sign Setting

    – 15 – ■ ■ ■ Installing indoor unit on high Filter sign setting Group control Each time button is pushed, indoor ceiling unit numbers in the control group change According to the installation condition, the fi lter sign In a group control, a remote controller can control up to cyclically.
  • Page 17: Test Run

    Test run Wireless remote controller Checking remote transmission 1. Push the ON/OFF button on the remote controller to ■ Before test run Wired remote controller NOTE determine that it works properly. • Pushing the TEST button once (for about one •...
  • Page 18: Maintenance

    – 17 – ▼Periodic Maintenance Maintenance • For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure effi cient operation of the air conditioner. When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
  • Page 19: Troubleshooting

    Troubleshooting ■ ■ Confi rmation and check Confi rmation of error log When an error occurred in the air conditioner, an error When an error occurred on the air conditioner, the code and indoor UNIT No. appear on the display part error log can be confi...
  • Page 20 – 19 – Check method On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided.
  • Page 21 Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote controller display Auxiliary code Operation Timer Ready Flash ─ ─ Indoor unit TCJ sensor error Indoor unit ─ ─...
  • Page 22 – 21 – Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote controller display Auxiliary code Operation Timer Ready Flash ─ Outdoor unit line address duplicated ─ ─...
  • Page 23 Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Wired remote controller display Auxiliary code Operation Timer Ready Flash 01:Comp. 1 side 02:Comp. 2 side Comp. position detective circuit system error IPDU 03:Comp.
  • Page 24: Specifi Cations

    – 23 – Declaration of Conformity Specifi cations Sound power level (dBA) Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. Model Weight (kg) 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Cooling Heating Amphur Muang, Pathumthani 12000, Thailand MMC-AP0157HP-E MMC-AP0187HP-E...
  • Page 25 Warnings on Refrigerant Leakage Important 2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15 % or larger than the respective fl oor spaces at the top or bottom of the door). Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas Outdoor unit...