Toshiba MMC-AP0188HPUL Service Manual page 37

Table of Contents

Advertisement

(Items necessary to perform the applied control at the local site are described.)
DN
Item
01
Filter display delay timer
02
Dirty state of filter
03
Central control address
04
Specific indoor unit
priority
06
Heating temp shift
0d
Existence of [AUTO]
mode
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
Louver type
(Air direction adjustment)
1E
Temp difference of [AUTO]
mode selection COOL →
HEAT, HEAT → COOL
28
Automatic restart of
power failure
2A
Selection of option/error
input (TCB-PCUC1E: CN3)
2E
HA terminal (CN61)
select
31
Ventilating fan control
32
TA sensor selection
33
Temperature unit select
Table: Function selecting CODE No. (DN)
0000 : None
0002 : 2500H
0004 : 10000H
0000 : Standard
0001 : High degree of dirt (Half of standard time)
0001 : No.1 unit
to
0099 : Unfixed
0000 : No priority
0000 : No shift
0002 : +3.6°F(2°C)
to
0000 : Provided
0001 : Not provided (Automatic selection from connected outdoor unit)
0000 : Heat pump
0001 : Cooling only (No display of [AUTO] [HEAT])
0007 : Ceiling
0000 : Unfixed
0001 : No.1 unit
to
0001 : No.1 unit
to
0000 : Individual
0002 : Follower unit of group
0000 : No louver
0002 : (1-way Cassette type, Ceiling type)
0003 : (2-way Cassette type)
0004 : (4-way Cassette type)
0000 : 0 deg
to
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None
0000 : Filter input
0002 : None
0000 : Usual
0002 : Fire alarm input
0000 : Unavailable
0000 : Body TA sensor
0000 : °C (at factory shipment) 0001 : °F
Description
0001 : 150H
0003 : 5000H
0064 : No.64 unit
0001 : Priority
0001 : +1.8°F(1°C)
0010 : +18°F(10°C)
(Up to +6 recommended)
0001 to 0034
0030 : No.30 unit
0064 : No.64 unit
0001 : Header unit of group
0001 : Swing only
0010 : 10 deg
0001 : Restart
0001 : Alarm input (Air washer, etc.)
0001 : Leaving-ON prevention control
0001 : Available
0001 : Remote controller sensor
- 37 -
At shipment
0002 : 2500H
0000 : Standard
0099 : Unfixed
0000 : No priority
0002 : +3.6°F(2°C)
(Floor type 0000: 0°C)
0001 : Not provided
0000 : Heat pump
Depending on model type
According to capacity type
0099 : Unfixed
0099 : Unfixed
0099 : Unfixed
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : None
0000 : Usual
(HA terminal)
0000 : Unavailable
0000 : Body TA sensor
0001 : °F