Toshiba MMC-AP0188HPUL Service Manual page 48

Table of Contents

Advertisement

Monitoring function of remote controller switch
When using the remote controller (Model Name: RBC-AMT32UL), the following monitoring
function can be utilized.
Calling of display
<Contents>
The temperature of each sensor of the remote controller, indoor unit and outdoor unit and the operating
status can be checked by calling the service monitor mode from the remote controller.
<Procedure>
1
CL
TEST
Push
+
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on and firstly the temperature of the CODE No.
2
TEMP.
Push
button to change CODE No.
to the CODE No. to be monitored.
For display code, refer to the following table.
3
UNIT LOUVER
Push
(left side button) button to change
to item to be monitored.
The sensor temperature of indoor unit or
outdoor unit in its refrigerant line and the
operating status are monitored.
4
TEST
Push
button to return the status to the
normal display.
TEMP.
2
FILTER
RESET
TEST
4
1
<Operation procedure>
1
2
- 48 -
is displayed.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
Returns to normal display
3
4
3

Advertisement

Table of Contents
loading

Table of Contents